2009-05-28 17:44:49 | 1. SHEET M-3. KEY NOTE #4 CALLS FOR SCREEN AT DRYER |
| EXHAUST OUTLET. SCREEN SHALL NOT BE INSTALLED AT DRYER |
| EXHAUST DUCT TERMINATION IN ACCORDANCE WITH FBC-M |
| 504.4. |
| 2. SHEET M-5. OUTSIDE AIR CALCULATIONS REFERENCE ASHRAE |
| 62.1-2007. THIS IS NOT THE CORRECT REFERENCE STANDARD. |
| PLEASE CONFIRM VENTILATION DESIGN IS IN COMPLIANCE WITH |
| ASHRAE 62.1-2004 IN ACCORDANCE WITH FBC-M 403.4 AND |
| FBC-M CHAPTER 15. |
| 3. SHEET M-7. PROVIDE AUXILIARY DRAIN PROTECTION. ON |
| DOWN-FLOW UNITS AND ALL OTHER COILS THAT DO NOT HAVE A |
| SECONDARY DRAIN AND DO NOT HAVE A MEANS TO INSTALL AN |
| AUXILIARY DRAIN PAN, A WATER-LEVEL MONITORING DEVICE |
| SHALL BE INSTALLED INSIDE THE PRIMARY DRAIN PAN IN |
| ACCORDANCE WITH FBC-M 307.2.3.1. |
| 4. CONDENSING UNIT IS SHOWN ON A PRE-ENGINEERED A/C |
| STAND. THIS IS DEFINED AS A STRUCTURAL COMPONENT IN |
| ACCORDANCE WIT FAC RULE 9B-72. PROVIDE PRODUCT APPROVAL |
| FOR THE STAND TO BE USED WITH INSTALLATION |
| INSTRUCTIONS. |
| 5. SHEET M-7. RTU NOTE #7 CALLS FOR CONDENSATE DRAINS |
| TO BE ROUTED TO THE NEAREST FLOOR DRAIN. CONDENSATE |
| SHALL NOT DISCHARGE INTO THE SANITARY SEWER SYSTEM IN |
| ACCORDANCE WITH CITY ORDINANCE. CONDENSATE PIPING SHALL |
| BE DISCHARGED AS SHOWN ON SHEET P-4 IN ACCORDANCE WITH |
| FBC-M 307.2.1. |
| 6. SHEET M-7. EQUIPMENT AND APPLIANCES THAT ARE EXPOSED |
| TO WIND SHALL BE DESIGNED AND INSTALLED TO RESIST WIND |
| PRESSURES AS DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| BUILDING CODE, BUILDING. PROVIDE MANUFACTURER???S DATA |
| OR OTHER SUCH SUPPORTING DOCUMENTATION SHOWING RTUS, |
| CONDENSERS AND ROOF CAPS ARE DESIGNED FOR WIND |
| RESISTANCE IN ACCORDANCE WITH FBC-M 301.12. |
| |
| PLEASE FEEL FREE TO CONTACT ME DURING NORMAL BUSINESS |
| HOURS IF YOU HAVE ANY QUESTIONS ABOUT THIS REVIEW. I |
| MAY BE REACHED AT 561-805-6650 OR BY EMAIL AT |
| [email protected] |
| |