Plan Review Notes
Plan Review Notes For Permit 09050371
Permit Number 09050371
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-06-02 16:13:20*****DENIED*****
  
 1. PROVIDE A POINT OF COMPASS FOR THE FLOOR PLAN SO AS
 IT RELATES TO PALM BEACH LAKES BOULEVARD.
  
 2.. ON SHEET A-4, INDICATE FIRE-RATED DOORS. BE ADVISED
 THAT FIRE-RATED DOORS AND ASSEMBLIES SHALL COMPLY WITH
 NFPA 80 - 1999 EDITION.
  
 3. ON SHEET E-8, FIRE ALARM NOTES, AMEND NOTE #7 TO
 INDICATE THAT: DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM.
  
 4. ON SHEET FS-1, UNDER FIRE SPRINKLER NOTES
 -COMPLIANCE, CODE EDITIONS AS FOLLOWS: NFPA 13 - 2002,
 NFPA 13R - 2002, NFPA 14 - 2003, NFPA 20 - 2003, AND
 NFPA 25 - 2002 SHALL BE REFERENCED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EASCH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW