Plan Review Notes For Permit 09050371 |
Permit Number |
09050371 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-05-28 21:12:10 | 1. ESSENTIAL ELECTRICAL SYSTEM TASK LIGHTING DOES NOT | | APPEAR TO BE INSTALLED IN ALL EXAM AND PROCEDURE AREAS | | PURSUANT TO THE REQUIREMENTS OF 517.33. | | 2. THE X RAY DISCONNECTING MEANS APPEARS TO BE LOCATED | | IN A DIFFERENT ROOM THAN THE X RAY CONTROL PANEL AND IS | | THEREFORE NOT READILY ACCESSIBLE PURSUANT TO 517.72 (B) | | 3. SHEET E-1 NOTE 8(B) NON-METALLIC CONDUIT MAY NOT BE | | RUN UNDERGROUND TO SERVE ANY PATIENT CARE AREAS | | PURSUANT TO 517.13.(A) AND (B). | | 4. ALL RECEPTACLES IN PATIENT CARE AREAS SHALL BE | | DESIGNATED AS HOSPITAL GRADE PURSUANT TO 517.18(B), | | 5. SHEET E-3.1. NOTE D. PLEASE ENSURE THAT RECEPTACLES | | IDENTIFIED AS BEING NECESSARY FOR THE ESSENTIAL | | ELECTRICAL SYSTEM MANDATED FOR THIS FACILITY PURSUANT | | TO 517.25 ARE PROVIDED IN EACH AREA SO DESIGNATED. IT | | APPEARS THAT ONLY CERTAIN EXAMINATION AND PROCEDURE | | ROOMS ARE APPROPRIATELY CIRCUITED. PLEASE CLARIFY. | | 6. INFORMATIONAL ONLY: SEPARATE APPLICATIONS AND | | PERMITS ARE REQUIRED FOR THE PROPOSED GENERATOR AND | | FIRE ALARM SYSTEM. | | PLEASE FEEL FREE TO CONTACT ME DURING NORMAL BUSINESS | | HOURS IF YOU HAVE ANY QUESTIONS ABOUT THIS REVIEW. I | | MAY BE REACHED AT 561-805-6650 OR BY EMAIL AT | | [email protected] |
|