Plan Review Notes For Permit 09050350 |
Permit Number |
09050350 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-05-26 16:32:38 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. SEE FBC108.1.3.6; TEMPORARY INSTALLATION OF | | HURRICANE PROTECTION OVER EXITS ARE PERMITTED IN GROUP | | R OCCUPANCY ONLY. THIS APPEARS TO BE GROUP B (SEE FBC | | CHAPTER 3). HOWEVER, SEE FBC1008.1.3.5. THE ROLLDOWN | | SHUTTER COULD BE CONSIDERED A "SECURITY GRILL" IF IT | | MEETS THE PROVISIONS OF THIS SECTION. PLEASE NOTE ON | | THE PLAN HOW THE ROLL UP SHUTTER CAN BE OPENED FROM THE | | INSIDE. | | | | 2. SEE SHEET 4 OF THE ROLL UP SHUTTER. A FACTOR OF .86 | | IS TO BE APPLIED IF THE EDGE DISTANCE IS LESS THAN 3 | | 1/2". | | | | 3. THIS APPEARS TO BE EXPOSURE C, FBC R301, FBC 1609, | | ASCE7-05. PLEASE REVISE;. | | | | 4. 3.2KSI REQUIRED FOR CONCRETE STRENGTH, SEE NOTE 9, | | PAGE 11 OF THE ACCORDION PRODUCT APPROVAL. HOW HAVE YOU | | DETERMINED THAT THE CONCRETE IN THIS STRUCTURE MEETS | | THIS REQUIREMENT? ANCHOR SPACING FOR CONCRETE BLOCK MAY | | BE USED IN LIEU OF SHOWING MINIMUM 3200PSI CONCRETE | | STRENGTH. | | |
|