Date |
Text |
2009-05-22 11:10:02 | DENIED |
| REFERENCE: |
| FBC-2007 W/2009 SUPPLEMENTS |
| FBC-2007 PLUMBING |
| FBC-2007 CHAPTER 1 |
| FBC-2007 CHAPTER 11 |
| |
| 1. SHT 'T' INDICATES THE PLANS WERE DESIGNED TO THE |
| 2004 FLORIDA BUILDING CODE. ALL PERMITS APPLIED FOR ON |
| OR AFTER MARCH 1, 2009 SHALL BE DESIGNED TO THE |
| FBC-2007 WITH 2009 SUPPLEMENTS. PLEASE CHANGE THE |
| DESIGN REFERENCES AND DESIGN THE PLANS TO CURRENT CODE |
| CYCLE. SECTION 106.1.1. |
| |
| 2. APPLICATION INDICATES THE SUITE NUMBERS AS 125 & |
| 150, BUT THE PLANS SHOW THE PROJECT TO BE IN SUITES 101 |
| & 103. PLEASE CORRELATE THE APPLICATION INFORMATION |
| WITH THE PLAN INFORMATION. SECTION 106.1.1. |
| |
| 3. PLUMBING PLANS ARE APPROVED BUT REVIEW RESULTS WILL |
| REMAIN IN FAILED STATUS UNTIL COMMENTS 1 & 2 ABOVE ARE |
| ADDRESSED. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |