Plan Review Notes
Plan Review Notes For Permit 09050247
Permit Number 09050247
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-05-28 13:48:14*****DENIED*****
  
 1. THE PROJECT DETAIL AS DESCRIBED ON THE APPLICATION
 IS FOR THE RECONFIGURATION OF SUITES 125 AND 150,
 HOWEVER THE PLANS REFLECT THAT THE PROJECT SCOPE OF
 WORK IS FOR SUITES 101 AND 103. PLEASE
 CORRELATE/CLARIFY.
  
 2. THE ACTUAL SUITE(S) SHALL BE INCLUDED IN THE ADDRESS
 LISTED IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 3. ON SHEET T, REFERENCE STANDARDS SHALL BE AS FOLLOWS:
 FLORIDA FIRE PREVENTION CODE 2007 EDITION, NFPA 101 -
 LIFE SAFETY CODE - 2006 EDITION, AND NFPA 1 - UNIFORM
 FIRE CODE - 2006 EDITION.
  
 4. ON SHEET E-2, ELECTRICAL NOTE #2, AMEND EDITION OF
 NFPA 101 FROM 2003 TO 2006.
  
 5. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHERS WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722