Plan Review Notes
Plan Review Notes For Permit 09050247
Permit Number 09050247
Review Stop E
Sequence Number 1
Notes
Date Text
2009-05-26 10:03:09**DENIED **
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING CODES ARE LISTED
 AT A MINIMUM.
 2007 FBC W/ 2009 REVISIONS.
 2006 NFPA-101
  
  
 2) NOTE: PLEASE LABEL ALL MAINS. ONLY ONE IS INDICATED.
 WILL THERE NOW BE A TOTAL OF 6 MAINS? THIS IS WHAT THE
 RISER APPEARS TO SHOW. PLEASE LABEL, 1 OF X, 2 OF X, 3
 OF X ETC. THE 1200 AMP MAIN IS SHOWN 1 OF 4, YET THIS
 APPEARS TO BE THE MAIN TO FEED GUTTER. THE TENANTS
 WOULD BE THEN TENANT MAINS?
 230.2E
  
 3) NOTE: PLEASE INDICATE CONDUCTORS FROM GUTTER TO
 METER AND METER TO NEW TENANT MAIN. PLEASE ALSO
 INDICATE A FLOATING NEUTRAL KIT IS REQUIRED IF THE 1200
 AMP MAIN INDEED FEEDS GUTTER.
 250.6,250.24,310.16,240.4.
  
 4) NOTE: PLEASE INCLUDE THE LOAD ON THE EXISTING MAIN
 WITH THE ADDITION OF THE NEW LOAD FOR TENANT.
 220. PLEASE BE SURE TO SHOW ALL CONTINUOUS LOADS AT
 125%.
  
 5) NOTE: PLEASE SEE CURRENT ADOPTED FLORIDA BUILDING
 CODE CHAPTER 13. A NOTE ON PLANS, MENTIONS THE SCONCES
 ARE NOT INCLUDED PER SECTION CITED. HOWEVER EVEN UNDER
 THE PREVIOUS CODES, THE SCONCES OR DECRETIVE TYPES OF
 FIXTURES WERE NEVER *EXEMPT*. THERE WAS AN ADDITIONAL
 ALLOWANCE FOR THOSE TYPES OF FIXTURE HOWEVER NOT
 EXEMPTED. IN BOTH CASES PLEASE SEE THE NEW ENERGY CODE
 AS THERE IS NO MORE ADDITIONAL ALLOWANCES FOR ANY
 DECRETIVE FIXTURES. ALL MUST BE FIGURED PER
 13-415.AB.5.
 TRADE OFF OF SPACES IS NOT LONGER PERMITTED EITHER.
 PLEASE BE SURE TO SEE THE ADOPTED REVISIONS TO CHAPTER
 13.
  
 6) NOTE: THE UNIT/SUITE NEEDS TO BE DETERMINED AS
 CORRECT. PERMIT APPLICATION STATES 125 AND 150, YET
 PLANS CALL FOR SUITE #103. PLEASE CORRELATE ALL OF
 THESE AND ADJUST AS NEEDED.
 WHEN RE-SUBMITTING PLANS IT IS IMPORTANT TO INDICATE
 THE CORRECTED SUITE NUMBER TO FRONT COUNTER STAFF IN
 ORDER FOR SYSTEM TO BE UPDATED WITH CORRECTED
 INFORMATION.
 FAC 61G15-23.002, 61G1-16.004, FBC 106.5
  
  
  
 * IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  