Plan Review Notes
Plan Review Notes For Permit 09050218
Permit Number 09050218
Review Stop B
Sequence Number 1
Notes
Date Text
2009-05-13 15:46:33RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2009
 REVISIONS.
  
 1- ACCORDION SHUTTERS DRAWINGS NO 05-578 SUBMITTED
 DON'T CORRESPOND TO FLORIDA FL10753-R1 PRODUCT APPROVAL
 SUBMITTED. GO TO WWW.FLORIDABUILDING.ORG TO DOWNLOAD
 CORRESPONDING DRAWINGS TO FLORIDA PRODUCT APPROVAL
 SUBMITTED.
  
 2- REVISE DESIGN PRESSURES CALCULATIONS SUBMITTED.
 ACCORDING TO THE 2009 REVISIONS TO THE 2007 FLORIDA
 RESIDENTIAL CODE, THIS BUILDING IS LOCATED ON EXPOSURE
 "C". SEE REVISED AND NEW SECTIONS R301.2.1.4 THRU
 R301.2.1.4.3 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 3- PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE ATTACHED
 SAMPLE. ALSO, CLEARLY MARK ON SHUTTERS DRAWINGS
 SPECIFIC MOUNTING CONDITIONS (EG: WALL MOUNTED, BUILT
 OUT, ETC) AND SPECIFIC ANCHOR TYPE AND SPACING TO BE
 USED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712