2009-07-03 08:25:09 | |
| ** DENIED 2ND REVIEW ** |
| |
| 1) NOTE: PLANS SUBMITTED DO NOT CONTAIN ANY DESIGN |
| PROFESSIONAL SIGNED, DATED OR SEALED ON ELECTRICAL |
| PLANS. PLEASE SEE 481.229, 471.003. PLANS ARE FOR A |
| COMMERCIAL HIGH-RISE MUST MEET THESE SECTIONS. |
| |
| 2) NOTE: PLEASE SEE BEDRM #2 WHICH STILL HAS MISSING |
| RECEPTACLE REQUIRED PER 210.52 FOR 2FT OR MORE OF WALL |
| SPACE. |
| |
| 3) NOTE: PREVIOUS NOTES WITH RESPECT TO THE REQUIRED |
| CIRCUITING AND SMALL APPLIANCE CIRCUITS FOR KITCHEN, |
| DINING AND AREAS OF THE LIKE. THE PLANS NOW INDICATE |
| ONLY ONE SMALL APPLIANCE CIRCUIT FOR THE ENTIRE |
| KITCHEN. TWO ARE REQUIRED AT A MINIMUM. AT THE TIME |
| THIS BUILDING WAS CONSTRUCTED THESE UNITS HAD TWO SMALL |
| APPLIANCE CIRCUITS AT A MINIMUM NOW ONLY SHOWS ONE IN |
| KITCHEN. |
| 210.52B1, 210.11C1, 220.52 |
| |
| 4) NOTE: PANEL SCHEDULE STILL INDICATES TWO WATER |
| HEATERS HOWEVER NONE ARE SHOWN ON PLANS. PLEASE KNOW |
| THAT ALL CONTINUOUS LOADS SHALL BE BASED AT 125%. |
| 422.13 |
| WHEN SHOWING THESE ITEMS ON PLANS, PLEASE BE SURE TO |
| INCLUDE THE NEW OR EXISTING DISCONNECTS PER 422.30,31 |
| ETC |
| |
| 5) NOTE: NOTES ON PLANS MENTION TO WIRE SMOKE ALARMS TO |
| EXISTING FIRE ALARM SYSTEM. PLEASE CHECK WITH THE FIRE |
| MARSHAL AS UNIT SINGLE STATION DEVICES SHOULD NOT BE |
| CONNECTED TO BASE BUILDING. IT MAY BE A TROUBLE SIGNAL |
| OF SOME TYPE. PLEASE CHECK WITH FIRE PLAN REVIEW. |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |