Plan Review Notes
Plan Review Notes For Permit 09050198
Permit Number 09050198
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-05-26 10:38:18*****DENIED*****
  
  
 1. STRUCTURES UNDERGGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. LIFE SAFETY TO COMPLY WITH NFPA 101 - 2006 EDITION
 WHICH HAS BEEN IN EFFECT SINCE DECEMBER 31ST, 2008.
  
 3. SPECIFY THE INTERIOR FINISH MATERIAL FOR THE NEW
 WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722