2009-05-22 08:47:22 | **DENIED ** |
| |
| 1) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS PER |
| MINIMUM CODE REQUIREMENTS. |
| PLEASE SEE DINING, BREAKFAST AREAS AND AREA OF THE LIKE |
| PER 210.52B1 ARE REQUIRED TO BE ON ONE OR MORE OF THE |
| SMALL APPLIANCE CIRCUITS. THE CIRCUIT IN ONE OF THESE |
| AREAS IS SHOWN AS CIRCUIT #17 WHICH IS A BEDROOM ARC |
| FAULT CIRCUIT WHICH IS NOT PERMITTED. |
| ANOTHER WOULD BE THE SMOKE ALARMS. PLEASE ALSO SEE |
| 210.12 FOR REQUIRED ARC FAULT PROTECTION. |
| PLEASE ALSO BE SURE TO SEE OTHER CIRCUITS ON PANEL |
| SCHEDULE WHICH DO NOT GO TO ANYTHING. 408.4. |
| |
| 2) NOTE: PLANS APPEAR TO HAVE LIGHT LOCATIONS WHICH ARE |
| SWITCHED FROM MORE THAN ONE LOCATION HOWEVER THE |
| SWITCHES ARE NOT SHOWN AS 3-WAYS. PLEASE ADJUST. NEC |
| 300. |
| FBC 106.1.1 |
| |
| 3) NOTE: PLEASE SEE 422.13 FOR STORAGE TYPE WATER |
| HEATERS WHICH REQUIRES LOAD TO BE FIGURED AT 125%. |
| |
| 4) NOTE: PLEASE BE SURE THE PLANS STATE THE FOLLOWING |
| CODES AT A MINIMUM. |
| 2002 NFPA-72 |
| 2007 FBC W/ 2009 REVISIONS |
| |
| 5) NOTE: PLEASE SEE 210.52 FOR RECEPTACLES SPACING. |
| THERE ARE SEVERAL LOCATIONS IN WHICH RECEPTACLES ARE |
| REQUIRED. SOME NEED TO BE ADDED AND SOME NEED TO BE |
| RELOCATED IN ORDER TO BE CODE COMPLIANT. |
| |
| 6) NOTE: PLEASE SEE 210.11C1, AND 220.52 FOR REQUIRED |
| LOAD TO BE FIGURED FOR THE ONE OR MORE SMALL APPLIANCE |
| CIRCUITS. THIS IS RELEVANT TO THE COMMENT NUMBER ONE |
| ABOVE. WHEN YOU HAVE MORE THAN TWO SMALL APPLIANCE |
| CIRCUITS FOR DINING ROOMS, AREAS LIKE BREAKFAST AREAS |
| AND THE LIKE, EACH ONE REQUIRES 1500 VA FOR EACH. |
| |
| 7) NOTE: PLEASE SEE 210.11C3 FOR RECEPTACLE MISSING |
| ALONG KITCHEN COUNTER SPACE. PLEASE ALSO SEE 210.8A6 |
| FOR REQUIRED GFCI PROTECTION. |
| |
| * IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |