Plan Review Notes For Permit 09050151 |
Permit Number |
09050151 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-06-16 08:21:35 | 2007 FBC | | INSTALL GENERATOR | | | | DENIED BY BUILDING | | | | 1) THE ENGINEERING CALCULATIONS AND PAD ANCHORING | | DRAWINGS FROM HILLMAN ENGINEERING INC. ARE REQUIRED TO | | HAVE THE ENGINEERS ORIGINAL SIGNATURE AND RAISED SEAL. | | FS 471.025 | | | | 2) THE CALCULATIONS FOR WIND LOAD REFERENCE THE 2004 | | FLORIDA BUILDING CODE AND ASCE 7-02. THE 2007 FLORIDA | | BUILDING CODE WENT INTO EFFECT ON MARCH 1,2009 AND ASCE | | 7-05 IS THE DESIGN STANDARD REFERENCED. PLEASE UP DATE | | ENGINEERING. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|