Plan Review Notes
Plan Review Notes For Permit 09050141
Permit Number 09050141
Review Stop B
Sequence Number 1
Notes
Date Text
2009-05-14 09:03:06RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2009
 REVISIONS.
  
 1- ACCORDING TO THE 2009 REVISIONS TO THE 2007 FLORIDA
 RESIDENTIAL CODE THIS BUILDING IS LOCATED ON EXPOSURE
 "C" NOT "B" AS SHOWN ON CALCULATIONS DONE BY THE
 ENGINEER. SEE REVISED SECTIONS R301.2.1.4 THRU
 R301.2.1.4.3 AND REVISE EXPOSURE AND DESIGN PRESSURES
 AS REQUIRED.
  
 2- SHUTTERS INSTALLATION SCHEDULE SUBMITTED:
 A) CLEARLY IDENTIFY EDGE DISTANCE FOR EACH OPENING.
 CLARIFY EDGE DISTANCE FOR OPENING #1 AT TOP AND BOTTOM.
 ONLY BOTTOM WAS SPECIFIED. CLARIFY WHY THE REST OF THE
 OPENINGS THE EDGE DISTANCE IS N/A? SPECIFY THE EDGE
 DISTANCE FOR EACH OPENING. DECREASE ANCHOR SPACING AS
 REQUIRED ON SHEET 5 OF 5 OF SHUTTERS DRAWINGS SUBMITTED
 IF THE EDGE DISTANCE IS LESS THAN 3" FOR CONCRETE AND
 CONCRETE BLOCK INSTALLATIONS.
  
 B) OPENINGS #2, #3, #4 AND #7 SPECIFY CONCRETE AS THE
 SUBSTRATE TO RECEIVE THE SHUTTERS AT TOP AND BOTTOM OF
 SHUTTERS. PROVIDE PROOF THAT WINDOW SILL IS POURED
 CONCRETE WITH 3000PSI CONCRETE NOT FILLED CONCRETE
 BLOCK OR USE CONCRETE BLOCK ANCHOR CHART.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712