Plan Review Notes For Permit 09050121 |
Permit Number |
09050121 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2009-12-17 13:29:13 | INTERIOR ALTERATION TO A PRIMARY FUNCTION WITHOUT A | | CHANGE IN OCCUPANCY. BOTH DISPROPORTIONATE COST AND | | TECHNICAL INFEASIBLITY APPLY TO THIS PROJECT. BASED | | UPON DISCUSSION AND REVIEW OF THE PROJECT ESTIMATED | | BUDGET AND DOCUMENTATION PROVIDED BY THE ARCHITECT OF | | RECORD IT NOW APPEARS CLEAR THAT THE COST TO COMPLETELY | | REBUILD A COMPLIANT BATHROOM WILL EXCEED 20% OF THE | | PROJECT COST. FURTHER IT IS A CHANGE IN USE WITHOUT A | | CHANGE IN OCCUPANCY IN ACCORDANCE WITH THE FLORIDA | | EXISTING BUILDING CODE. SINCE THE CHANGE IN USE DOES | | NOT CREATE A MORE INTENSIVE USE OF THE EXISTING | | PLUMBING FIXTURES THE EXISTING FIXTURES ARE DEEMED | | "COMPLIANT" BY RULE. ACCORDINGLY THE EXISTING BOTTLE | | WATER DISPENSER IS ALLOWED TO REMAIN AS THE SOLE | | DRINKING FOUNTAIN PURSUANT TO THE PRIOR RULE. THEREFORE | | ONLY THE IMPROVEMENTS TO ACCESIBILITY AS PROPOSED BY | | THE ARCHITECT ARE REQUIRED AND ARE DEEMED ACCEPTABLE TO | | THIS REVIEWER AT THE TIME OF REVIEW. |
|