Plan Review Notes
Plan Review Notes For Permit 09050121
Permit Number 09050121
Review Stop M
Sequence Number 3
Notes
Date Text
2009-11-06 11:18:31PROVISO:
  
 PROVIDE A MINIMUM OF 400 CFM OUTSIDE AIR FOR THE
 PROPOSED NEW USE OF THIS SPACE IN ACCORDANCE WITH
 FBC-EB 901.2 AND 909.1. A TEST AND BALANCE REPORT SHALL
 BE PROVIDED TO VERIFY VENTILATION RATES PRIOR TO FINAL
 INSPACTION IN ACCORDANCE WITH FBC-M 403.3.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: