Date |
Text |
2009-11-19 11:34:27 | |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005 |
| NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED, |
| CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} FROM PREVIOUS REVIEW WITH ARTICLE FOR EXPLANATION: |
| 1} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE |
| INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A |
| SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING |
| SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD |
| DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR |
| LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING |
| FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN |
| USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING |
| POWER IDENTIFIED IN ACCORDANCE WITH SECTION |
| 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING |
| POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH |
| SECTION13-415.B.1*** SHOW COMPLIANCE ON THE PLAN. THIS |
| CAN BE DEMONSTRATED ON THE PLANS INDICATING THE |
| WATTAGES OF THE LUMINAIRES CHOSEN FOR THE PROJECT |
| CONFORM TO THE DENSITY REQUIREMENTS. INDICATE WATTAGES |
| ON THE FIXTURE SCHEDULE TO CORRELATE WITH THE ONES IN |
| THE CALCULATIONS. |
| |
| 2} EMERGENCY ILLUMINATION PER NFPA-101 7.8 (2006), AND |
| CIRCUITED PER 700.12 NEC (F)(4). INDICATE SAME ON |
| PLANS. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |
| |