Date |
Text |
2009-08-14 13:56:29 | DENIED |
| REFERENCE: |
| FBC-2007 W/2009 SUPPLEMENTS |
| FBC-2007 EXISTING BUILDING |
| FBC-2007 PLUMBING |
| FBC-2007 CHAPTER 1 |
| FBC-2007 CHAPTER 11 |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| 1. SHT A-1 THE PROPOSED TOILET ROOM SHALL BE |
| ACCESSIBLE. THE MINIMUM WIDTH FOR AN ACCESSIBLE TOILET |
| ROOM IS 5'3" FINISHED WIDTH. THE PLANS SHOW 5'0". |
| SECTION 405.3.1 & FIG. 28. |
| *****NO RESPONSE, COMMENT NOT ADDRESSED. |
| |
| 2. SHT A-1 SHOW THE TURNING AREA IN THE ACCESSIBLE |
| TOILET ROOM. SECTION 11-4.22.3. |
| *****NO RESPONSE, COMMENT NOT ADDRESSED. |
| |
| 3. SHT A-1. BATHROOM NOTES #3 INDICATES THE GRAB BAR |
| BEHIND THE W/C TO BE 24 INCHES LONG AND MAXIMUM 12" |
| FROM THE CORNER. THE GRAB BAR BEHIND THE W/C IS |
| REQUIRED TO BE A MINIMUM 36" LONG AND A MAXIMUM 6" FROM |
| THE CORNER. SEE SECTION 11-4.16.4. |
| *****NO RESPONSE, COMMENT NOT ADDRESSED. |
| |
| 4. OK |
| 5. OK |
| |
| 6. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED. |
| PLEASE SHOW THE LOCATION OF THE REQUIRED DRINKING |
| FOUNTAIN. |
| *****NO RESPONSE, COMMENT NOT ADDRESSED. |
| |
| ********NEW COMMENT******** |
| |
| 1B. SUBMIT A DETAIL FOR THE REQUIRED DRINKING FOUNTAIN |
| SHOWING COMPLIANCE WITH SECTION 11-4.15 WITH ALL |
| SUBSECTIONS AS WELL AS SECTION 11-4.1.3(10)(A) |
| PROVISIONS FOR THOSE WHO HAVE DIFFICULTY BENDING OR |
| STOOPING. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| |
| |
| |