Plan Review Notes
Plan Review Notes For Permit 09050121
Permit Number 09050121
Review Stop E
Sequence Number 2
Notes
Date Text
2009-08-26 17:01:50 
  
  
  
  
 ** DENIED REVIEW 2ND REVIEW **
  
 ** THERE IS STILL INFORMATION NEEDED FOR MINIMUM CODE
 COMPLIANCE. THERE IS INFORMATION NOT YET SUBMITTED.
 THERE ARE NEW COMMENTS BASED ON SOME NEW INFORMATION.
 ** THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW AS
 THERE ARE ITEMS NOT YET SUBMITTED FOR CODE COMPLIANCE.
  
 1) NOTE: NO LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.AB.5, 13-400.B.0.4, 13-415.B.1, .2.2 SUBMITTED.
 MUST MEET MINIMUM PRESCRIPTIVE REQUIREMENTS AS ORIGINAL
 NOTED.
 ** KEEP IN MIND ALL FIXTURES ON LEGEND NEED TO BE
 SPECIFIC. BASED ON THE TYPE OF FIXTURES SHOWN THE
 WATTAGE WOULD BE OVER THE ALLOWANCES UNDER FBC CHAPTER
 13
  
 2) NOTE: EXTERIOR LIGHTING CONTROLS STATES * TIMER*.
 PLEASE BE SURE TO SEE 13-415.AB.1.4 FOR TYPE OF
 CONTROLS REQUIRED AND INDICATE.
  
 3) NOTE: ALL EMERGENCY LIGHTING SHOWN ON PLANS SHALL BE
 CIRCUITED PER 700.12F.
  
 4) NOTE: THERE NEEDS TO BE A SYMBOL LEGEND FOR DEVICES.
 NOTE ON PLANS MENTIONS ALL SWITCHES TO BE * MOTION
 SENSOR TYPE*. IS THIS CORRECT? ARE THESE MEANT TO BE
 *OCCUPANCY SENSORS?
  
 5) NOTE: NO PANEL SCHEDULE OR SIZE OF NEW OR EXISTING
 PANEL(S), LOCATION(S) OF SERVICE ETC SUBMITTED. CAN NOT
 VERIFY SEVERAL ITEMS FOR CODE COMPLIANCE AT THIS TIME.
 NO NEW LOCATIONS FOR RECEPTACLES. THERE IS A DEMO PLAN
 HOWEVER NO NEW POWER PLAN.
 LOADS, CIRCUITS, OVER CURRENT PROTECTION ETC.
 220,215.3,230.42,408.4,310.16 ETC
 220.12,220.14,220.44,220.43,220.42 ETC
 THERE ARE TOO MANY CODE SECTIONS TO REFERENCE.
 FBC 106.1.1,106.1.2,106.3.5.1.2 ADDITIONAL INFORMATION,
 CLARITY.
  
 6) NOTE: NEW OR EXISTING SIGN CIRCUIT PER 600.5
  
 7) NOTE: PLANS INDICATE NEW 60 GALLON WATER HEATER. SEE
 422.13 FOR SIZING OF BRANCH CIRCUITS AND CONTINUOUS
 LOAD AT 125%.
  
 8) NOTE: PLANS SHOW NEW PROPOSED WASHER AND DRYER
 HOWEVER NO ELECTRICAL RECEPTACLES, INFORMATION, LOADS,
 CIRCUITING ETC. SOME OF THE SAME INFORMATION AS NOTED
 ABOVE IN COMMENT #5.
 220.44,220.54
  
 9) NOTE: THERE IS A HOLD IN SYSTEM. THE ORIGINAL PERMIT
 APPLICATION WAS NOT SUBMITTED BACK WITH PLANS. THIS IS
 STILL NEEDED AND REQUIRED.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  