2009-08-26 17:01:50 | |
| |
| |
| |
| |
| ** DENIED REVIEW 2ND REVIEW ** |
| |
| ** THERE IS STILL INFORMATION NEEDED FOR MINIMUM CODE |
| COMPLIANCE. THERE IS INFORMATION NOT YET SUBMITTED. |
| THERE ARE NEW COMMENTS BASED ON SOME NEW INFORMATION. |
| ** THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW AS |
| THERE ARE ITEMS NOT YET SUBMITTED FOR CODE COMPLIANCE. |
| |
| 1) NOTE: NO LIGHTING PERFORMANCE CALCULATIONS PER |
| 13-415.AB.5, 13-400.B.0.4, 13-415.B.1, .2.2 SUBMITTED. |
| MUST MEET MINIMUM PRESCRIPTIVE REQUIREMENTS AS ORIGINAL |
| NOTED. |
| ** KEEP IN MIND ALL FIXTURES ON LEGEND NEED TO BE |
| SPECIFIC. BASED ON THE TYPE OF FIXTURES SHOWN THE |
| WATTAGE WOULD BE OVER THE ALLOWANCES UNDER FBC CHAPTER |
| 13 |
| |
| 2) NOTE: EXTERIOR LIGHTING CONTROLS STATES * TIMER*. |
| PLEASE BE SURE TO SEE 13-415.AB.1.4 FOR TYPE OF |
| CONTROLS REQUIRED AND INDICATE. |
| |
| 3) NOTE: ALL EMERGENCY LIGHTING SHOWN ON PLANS SHALL BE |
| CIRCUITED PER 700.12F. |
| |
| 4) NOTE: THERE NEEDS TO BE A SYMBOL LEGEND FOR DEVICES. |
| NOTE ON PLANS MENTIONS ALL SWITCHES TO BE * MOTION |
| SENSOR TYPE*. IS THIS CORRECT? ARE THESE MEANT TO BE |
| *OCCUPANCY SENSORS? |
| |
| 5) NOTE: NO PANEL SCHEDULE OR SIZE OF NEW OR EXISTING |
| PANEL(S), LOCATION(S) OF SERVICE ETC SUBMITTED. CAN NOT |
| VERIFY SEVERAL ITEMS FOR CODE COMPLIANCE AT THIS TIME. |
| NO NEW LOCATIONS FOR RECEPTACLES. THERE IS A DEMO PLAN |
| HOWEVER NO NEW POWER PLAN. |
| LOADS, CIRCUITS, OVER CURRENT PROTECTION ETC. |
| 220,215.3,230.42,408.4,310.16 ETC |
| 220.12,220.14,220.44,220.43,220.42 ETC |
| THERE ARE TOO MANY CODE SECTIONS TO REFERENCE. |
| FBC 106.1.1,106.1.2,106.3.5.1.2 ADDITIONAL INFORMATION, |
| CLARITY. |
| |
| 6) NOTE: NEW OR EXISTING SIGN CIRCUIT PER 600.5 |
| |
| 7) NOTE: PLANS INDICATE NEW 60 GALLON WATER HEATER. SEE |
| 422.13 FOR SIZING OF BRANCH CIRCUITS AND CONTINUOUS |
| LOAD AT 125%. |
| |
| 8) NOTE: PLANS SHOW NEW PROPOSED WASHER AND DRYER |
| HOWEVER NO ELECTRICAL RECEPTACLES, INFORMATION, LOADS, |
| CIRCUITING ETC. SOME OF THE SAME INFORMATION AS NOTED |
| ABOVE IN COMMENT #5. |
| 220.44,220.54 |
| |
| 9) NOTE: THERE IS A HOLD IN SYSTEM. THE ORIGINAL PERMIT |
| APPLICATION WAS NOT SUBMITTED BACK WITH PLANS. THIS IS |
| STILL NEEDED AND REQUIRED. |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |