Plan Review Notes For Permit 09050121 |
Permit Number |
09050121 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-05-15 22:37:36 | *****DENIED***** | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 | | EDITION. | | | | 2. THE 2007 FLORIDA FIRE PREVENTION FIRE CODE (BASED ON | | NFPA 101 - LIFE SAFETY CODE - 2006 EDITION AND NFPA 1 | | -UNIFORM FIRE CODE - 2006 EDITION) SHALL BE REFERENCED. | | | | 3. ON SHEET A-1, PROVIDE A DIRECTIONAL GUIDE INDICATIVE | | TO THE LAYOUT OF THE BUILDING. | | | | 4. IN THE FIXTURE LEGEND ON SHEET A-1, PLEASE | | VERIFY/CLARIFY AS TO WHETHER THE SYMBOL FOR THE WALL | | MOUNT EXIT LIGHT SHOULD BE EMERGENCY LIGHTS INSTEAD. | | | | 5. WHEN COMPARING THE PROPOSED CEILING PLAN WITH THE | | PROPOSED FLOOR PLAN AS SHOWN ON SHEET A-1, THERE | | APPEARS THAT A CEILING MOUNT EXIT LIGHT/EMERGENCY COMBO | | ABOVE A RESTROOM DOOR. HOW WILL PATRONS NOT BE CONFUSED | | AS TO THE TRUE LOCATION OF THE EXIT. | | | | 6. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE | | EXTINGUISHER(S) WHICH SATISFY THE 75 TRAVEL DISTANCE. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|