Plan Review Notes
Plan Review Notes For Permit 09050121
Permit Number 09050121
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-05-15 22:37:36*****DENIED*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. THE 2007 FLORIDA FIRE PREVENTION FIRE CODE (BASED ON
 NFPA 101 - LIFE SAFETY CODE - 2006 EDITION AND NFPA 1
 -UNIFORM FIRE CODE - 2006 EDITION) SHALL BE REFERENCED.
  
 3. ON SHEET A-1, PROVIDE A DIRECTIONAL GUIDE INDICATIVE
 TO THE LAYOUT OF THE BUILDING.
  
 4. IN THE FIXTURE LEGEND ON SHEET A-1, PLEASE
 VERIFY/CLARIFY AS TO WHETHER THE SYMBOL FOR THE WALL
 MOUNT EXIT LIGHT SHOULD BE EMERGENCY LIGHTS INSTEAD.
  
 5. WHEN COMPARING THE PROPOSED CEILING PLAN WITH THE
 PROPOSED FLOOR PLAN AS SHOWN ON SHEET A-1, THERE
 APPEARS THAT A CEILING MOUNT EXIT LIGHT/EMERGENCY COMBO
 ABOVE A RESTROOM DOOR. HOW WILL PATRONS NOT BE CONFUSED
 AS TO THE TRUE LOCATION OF THE EXIT.
  
 6. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFY THE 75 TRAVEL DISTANCE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  