2009-05-15 13:11:33 | BUILDING PLAN REVIEW |
| PERMIT: 09050121 |
| ADD: 5115 S DIXIE HWY |
| CONT: PRO-BUILT |
| TEL: (561)444-3008 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| BUILDING WITH 2009 SUPPLEMENTS, 2007 EXISTING BUILDING |
| CODE W/ 2009 SUPPLEMENTS, PLEASE UPDATE APPLICABLE |
| CODES. |
| |
| 2) CODE ANALYSIS INDICATES THIS TO BE A TYPE IV |
| BUILDING WHICH IS HEAVY TIMBER, PLEASE CORRECT, TABLE |
| 503. |
| |
| 3) SHEET A-1 DOOR# 1 DOES NOT INDICATE THIS IS A NEW |
| CUT IN OPENING, PLEASE SEE INTERIOR DEMO PERMIT |
| 09040632 AND NOTE # 5 WHICH DEALS WITH THE NEW DOORWAY |
| BEING CUT INTO THE WALL AND BUILDING PROVISO: DEMO |
| NOTE# 5 TO BE DETERMINED BY ZONING DEPARTMENT , BLDG IS |
| OK WITH SET BACK REQUIREMENTS TABLE 602. THE NEW PLANS |
| FAIL TO INDICATE HOW THE BLOCK WALL WILL BE FITTED WITH |
| COLUMNS AND EITHER BEAM OR LINTEL. ALSO MISSING PRODUCT |
| APPROVALS FOR THE NEW LINTEL & DOOR OPENING. |
| |
| 4) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING |
| REPORTS ARE AS FOLLOWS: |
| 4A) LINTEL |
| 4B) EXTERIOR DOOR |
| |
| 5) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 6) THE SWING RESTROOM DOOR AND DOOR # 4 ARE MISSING THE |
| REQUIRED 18" LATCH SIDE. |
| 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM |
| MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC |
| OR POWER-ASSISTED SHALL BE AS SHOWN IN |
| FIG. 25. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED |
| CLEARANCES SHALL BE CLEAR & LEVEL. |
| |
| 7) WINDOW E IS A HAZARDOUS LOCATION: WILL REQUIRE |
| SAFETY GLAZING. 2406.3(6). |
| |
| 8) THIS MAY BE A CHANGE OF OCCUPANCY : BEFORE A PERMIT |
| TO CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID |
| TO PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS |
| MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID |
| RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL |
| (561)233-5025 FOR MORE INFORMATION. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |