Notes
Date Text
2009-05-11 14:17:16****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SHUTTER MOUNTING CONNECTION TYPE STATES BUILDOUT,
 BUT INSIDE MOUNT IS ALSO INDICATED ON PRODUCT APPROVAL.
 THE SPAN IS LESS THAN THE OPENING; THE SPAN FOR AN
 INSIDE MOUNT IS SMALLER BUT SHOULD BE LARGER FOR A
 BUILD OUT. ANCHOR SPACING IS DETERMINED BY MOUNTING
 TYPE AND DESIGN PRESSURE; PLEASE CLARIFY SO THAT CODE
 COMPLIANCE CAN BE DETERMINED. IF TOP AND BOTTOM USE
 DIFFERENT MOUNTING DETAILS, PLEASE SPECIFY BOTH.
  
 2. CONCRETE IS SPECIFIED AS SUBSTRATE; IS THIS INTO A
 PATIO SLAB? THE SLABS FOR HOUSES IN THIS DEVELOPMENT
 WERE TYPICALLY 2500PSI, NOT 3000 PSI (MINIMUM STRENGTH
 REQUIREMENT ON PRODUCT APPROVAL, SHEET 5).
  
 3. A .71 FACTOR FOR 2" EDGE DISTANCE TO BE APPLIED TO
 ANCHOR SPACING. PLEASE CONFIRM THAT THIS HAS BEEN
 APPLIED.