Plan Review Notes
Plan Review Notes For Permit 09050076
Permit Number 09050076
Review Stop B
Sequence Number 3
Notes
Date Text
2009-07-22 22:25:02****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLEASE PROVIDE EVIDENCE THAT THIS PROPERTY IS
 GREATER THAN 1500' FROM THE INTERCOASTAL. THE
 CONTRACTOR PROVIDED A STATEMENT THAT THE PROPERTY IS
 GREATER THAN 1500', AND THE PERMIT WAS ISSUED BASED ON
 THAT STATEMENT. HOWEVER, MEASUREMENTS PROVIDED BY OUR
 GIS SHOWS THAT THIS PROPERTY IS APPROXIMATELY 1400'
 FROM THE INTERCOASTAL. ON WHAT INFORMATION DID THE
 CONTRACTOR BASE THAT STATEMENT? PLEASE PROVIDE EVIDENCE
 OF EXPOSURE B CONDITIONS OR REVISE INSTALLATION
 SCHEDULE FOR EXPOSURE C.
  
 2. OPENING 3 STATES THAT IT WILL BE INSTALLED
 HORIZONTALLY, THE HORIZONTAL DIMENSION (WXH) IS 95",
 BUT THE SPAN IS 40"? INFORMATION IS NOT CONSISTENT.
 THIS COMMENT APPLIES TO OTHER OPENINGS.
  
 3. SEE OPENINGS 1 AND 2, HOW CAN THE SPAN BE THE SAME
 AS THE OPENING SIZE WITH A WALL MOUNT AND A .75 EDGE
 DISTANCE? PLEASE EITHER EXPLAIN OR REVISE.