2009-06-10 16:54:27RESIDENTIAL (R3) GENERATOR, BUILDING REVIEW CHECKLIST.
  
 1- SURVEY SHOWS A 4'-8" X 5'-0" CONCRETE SLAB, WHILE
 ENGINEERED DRAWINGS CALLS FOR 4'-8" X 10'-0" MINIMUM
 CONCRETE SLAB SIZE. COORDINATE INFORMATION AS REQUIRED
 TO MATCH.
 ALSO, COORDINATE WITH ZONING COMMENTS.
  
 2- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 VALUE TO INCLUDE GENERATOR, PROFESSIONAL ENGINEER FEES,
 ALL LABOR AND MATERIAL REQUIRED TO PERFORM THE JOB. AND
 THE CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY
 SEC. 108.3 CITY AMENDMENTS TO FBC. UPDATE VALUATION AS
 REQUIRED.
  
 3- NEEDS RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  
  