Plan Review Notes
Plan Review Notes For Permit 09050066
Permit Number 09050066
Review Stop E
Sequence Number 1
Notes
Date Text
2009-05-18 14:02:42**DENIED REVIEW **
  
 1) NOTE: PLEASE SEE FBC R313 WHICH REQUIRES ALL SMOKE
 DETECTION SYSTEMS TO BE BROUGHT UP TO CURRENT CODES.
 11.5.1, 11.8.3. PLANS STATE SD AND NOTES FOR SMOKE
 DETECTORS.
 SMOKE DETECTORS ARE ONLY DEVICES WHICH DETECT AND DO
 NOT SOUND AN ALARM. IF THIS IS THE CASE PLEASE IDENTIFY
 THE HORN/SIREN DEVICE LOCATIONS. IF THESE ARE INDEED
 SMOKE ALARM DEVICES WHICH DETECT AND SOUND AN ALARM,
 PLEASE ADJUST THE TYPE OF DEVICE IN NOTES AND ON PLANS.
 PLEASE ALSO SEE 210.12 FOR REQUIRED ARC FAULT
 PROTECTION.
  
 ** PLEASE KEEP IN MIND IF THERE IS ANY GAS APPLIANCES
 OR ATTACHED GARAGE FS 553.885 REQUIRES CARBON MONOXIDE
 DETECTION.
  
  
 2) NOTE: PLANS STATE A NEW SERVICE HOWEVER NO RISER
 DIAGRAM WAS SUBMITTED FOR THE SIZE OF SERVICE,
 CONDUCTORS, GROUNDING , AIC RATINGS, ETC.
 110.9,250.50,310.16,310.15B6 ETC
 PLEASE SEE 2005 NEC
  
 3) NOTE: PLEASE SHOW LOCATION OF PANEL COMPARED TO
 KITCHEN COUNTER SPACE TO VERIFY 110.26
  
 4) NOTE: PLAN STATES TO REPLACE ALL STANDARD
 RECEPTACLES WITH GFI DEVICES. PLEASE EXPLAIN AND SHOW
 LOCATIONS.
 WHY ARE ALL DEVICES BEING CHANGED TO GFICI? 210.8A
  
 5) NOTE: VALUE FOR SCOPE OF WORK IS LOW.
 FBC 108.3
  
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  