2009-05-18 14:02:42 | **DENIED REVIEW ** |
| |
| 1) NOTE: PLEASE SEE FBC R313 WHICH REQUIRES ALL SMOKE |
| DETECTION SYSTEMS TO BE BROUGHT UP TO CURRENT CODES. |
| 11.5.1, 11.8.3. PLANS STATE SD AND NOTES FOR SMOKE |
| DETECTORS. |
| SMOKE DETECTORS ARE ONLY DEVICES WHICH DETECT AND DO |
| NOT SOUND AN ALARM. IF THIS IS THE CASE PLEASE IDENTIFY |
| THE HORN/SIREN DEVICE LOCATIONS. IF THESE ARE INDEED |
| SMOKE ALARM DEVICES WHICH DETECT AND SOUND AN ALARM, |
| PLEASE ADJUST THE TYPE OF DEVICE IN NOTES AND ON PLANS. |
| PLEASE ALSO SEE 210.12 FOR REQUIRED ARC FAULT |
| PROTECTION. |
| |
| ** PLEASE KEEP IN MIND IF THERE IS ANY GAS APPLIANCES |
| OR ATTACHED GARAGE FS 553.885 REQUIRES CARBON MONOXIDE |
| DETECTION. |
| |
| |
| 2) NOTE: PLANS STATE A NEW SERVICE HOWEVER NO RISER |
| DIAGRAM WAS SUBMITTED FOR THE SIZE OF SERVICE, |
| CONDUCTORS, GROUNDING , AIC RATINGS, ETC. |
| 110.9,250.50,310.16,310.15B6 ETC |
| PLEASE SEE 2005 NEC |
| |
| 3) NOTE: PLEASE SHOW LOCATION OF PANEL COMPARED TO |
| KITCHEN COUNTER SPACE TO VERIFY 110.26 |
| |
| 4) NOTE: PLAN STATES TO REPLACE ALL STANDARD |
| RECEPTACLES WITH GFI DEVICES. PLEASE EXPLAIN AND SHOW |
| LOCATIONS. |
| WHY ARE ALL DEVICES BEING CHANGED TO GFICI? 210.8A |
| |
| 5) NOTE: VALUE FOR SCOPE OF WORK IS LOW. |
| FBC 108.3 |
| |
| |
| |
| |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |