Plan Review Notes For Permit 09050045 |
Permit Number |
09050045 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-05-05 09:32:17 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | REVIEW UNDER 2007 FLORIDA BUILDING CODE-EXISTING | | BUILDING. | | | | 1- FLAT ROOF: | | A) CLEARLY MARK WHICH APPROVED ASSEMBLY IS GOING TO BE | | INSTALLED. | | | | B) ON SELECTED ASSEMBLY IDENTIFY SPECIFIC BASE SHEET | | FASTENING OPTION. | | | | C) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | LIMITATION #7. | | NOTE: IF SELECTED ASSEMBLY IS REGULATED BY GENERAL | | LIMITATION #9, THEN IT MAY NOT BE USED IN THIS AREA | | BECAUSE IT MAY NOT RESIST THE UPLIFT LOADS. | | | | 2- THIS HOUSE HAS MORE THAN $300,000 VALUE. NEED TO | | PROVIDE DOCUMENTATION SHOWING COMPLIANCE WITH THE ROOF | | TO WALL CONNECTIONS AS REQUIRED BY SEC. 611.8 AND SEC. | | 611.8.1 OF 2007 FLORIDA BUILDING CODE- EXISTING | | BUILDING. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|