Plan Review Notes
Plan Review Notes For Permit 09050045
Permit Number 09050045
Review Stop B
Sequence Number 1
Notes
Date Text
2009-05-05 09:32:17RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2007 FLORIDA BUILDING CODE-EXISTING
 BUILDING.
  
 1- FLAT ROOF:
 A) CLEARLY MARK WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED.
  
 B) ON SELECTED ASSEMBLY IDENTIFY SPECIFIC BASE SHEET
 FASTENING OPTION.
  
 C) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7.
 NOTE: IF SELECTED ASSEMBLY IS REGULATED BY GENERAL
 LIMITATION #9, THEN IT MAY NOT BE USED IN THIS AREA
 BECAUSE IT MAY NOT RESIST THE UPLIFT LOADS.
  
 2- THIS HOUSE HAS MORE THAN $300,000 VALUE. NEED TO
 PROVIDE DOCUMENTATION SHOWING COMPLIANCE WITH THE ROOF
 TO WALL CONNECTIONS AS REQUIRED BY SEC. 611.8 AND SEC.
 611.8.1 OF 2007 FLORIDA BUILDING CODE- EXISTING
 BUILDING.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712