Plan Review Notes
Plan Review Notes For Permit 09050021
Permit Number 09050021
Review Stop E
Sequence Number 3
Notes
Date Text
2009-06-22 14:59:28 
 ** DENIED REVISIONS **
  
 1) NOTE: PLANS STILL SHOWS SYSTEMS FROM TWO SEPARATE
 LEGAL PROPERTIES AND OWNERS CROSSING ONTO ONE LOCATION.
 NONE OF THESE ITEMS WERE ON PREVIOUS PLANS.
 THE PLANS NOW INDICATE GATES WITH CONTROLS TO TRI-RAIL
 STATION. THIS WOULD ALSO HAVE ELECTRICAL EQUIPMENT WITH
 POWER FROM TWO SOURCES.
 PLEASE ALSO SEE 250 FOR SYSTEMS REQUIRED TO BE BONDED.
 250.90,250.92,250.94, ETC
 ARE THE GATES ALSO FED FROM THE LIGHTING CIRCUIT?
  
 2) NOTE: PLEASE KNOW THAT ANY ACCESS GATES AND FENCING
 SHALL BE UNDER SEPARATE PERMITS. PLEASE BE SURE TO
 CONTACT THE FIRE MARSHAL FOR ANY MINIMUM WIDTHS FOR
 FIRE VEHICLE EQUIPMENT. THESE WERE NOT ON PREVIOUS
 PLANS WHICH WERE RED LINED FOR UNDERGROUND CONDUITS
 ONLY.
 PLEASE BE SURE TO SUBMIT THE GATE OPERATOR SPEC SHEETS
 WHEN SUBMITTING FOR PERMIT. 110.3.
  
 3) NOTE: PLEASE CLARIFY THE CONDUCTORS TO THE SERVICE
 AND MAIN.
 RISER NOTES 3-#1 AND #8 G. IS THIS THE NEUTRAL/GROUNDED
 CONDUCTOR?
 NO EQUIPMENT GROUNDING BEFORE FIRST MEANS OF
 DISCONNECT. PLEASE SEE THAT THE RISER DOES NOT INDICATE
 LOCATION IN WHICH THE MINI-ZONE TRANSFORMER WILL BE
 GROUNDED PER 250.50,250.66,250.20,250.30
  
 4) NOTE: THE PANEL SCHEDULE FOR H AND RISER DOES NOT
 INDICATE THE CONDUCTORS FROM THE PANEL TO THE MINI-ZONE
 PANEL UNIT.
 310.16, 240.4
  
 5) NOTE: PLEASE SEE 450.3 AS THE MAXIMUM OVER CURRENT
 PROTECTION TO THE TRANSFORMER SHALL BE 125%.
 ( SEE NOTE #5) AS NOTED ON TABLE.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THE
 TRANSFORMER. PLEASE BE SURE THE SPECS INDICATE A
 LISTING FROM A RECOGNIZED NRTL.
 110.3,90.7
  
 6) NOTE: PLEASE BE SURE THE ADOPTED RELEVANT CODES ARE
 STATED ON PLANS. THE PLANS STATE THE 2008 SFBC ( SOUTH
 FLORIDA BUILDING CODE). THE STATE OF FLORIDA IS UNDER
 THE FLORIDA BUILDING CODE PER FS 553.73. THIS WAS
 BEGINNING IN 2002.
  
 PLEASE BE SURE THE PLANS CONTAIN THE FOLLOWING CODES
 BASED ON THE PERMIT APPLICATION DATE.
 2007 FBC W/ 2009 REVISIONS.
 2005 NFPA-70 (NEC).
  
 7) NOTE: PLEASE REVISE THE COLOR CODING ON THE PLANS
 FOR THE 277/480V SYSTEM TO BROWN, PURPLE, AND YELLOW.
 THIS AHJ HAD LOCAL TECHNICAL AMENDMENTS FOR SEVERAL
 DECADES FOR COLOR CODING OF ELECTRICAL SYSTEMS AS THE
 NEC DID NOT PROVIDE COLOR CODING. THE NEC DOES USE THE
 COLOR OF ORANGE FOR OPEN DELTA HIGH LEG SYSTEM
 IDENTIFICATION. THE SYSTEM AS SHOWN ON PLANS IS NOT A
 HIGH-LEG SYSTEM. IN KEEPING WITH THE IDENTIFICATION OF
 OTHER SYSTEMS IN THIS JURISDICTION PLEASE ADJUST.
 90.4
 * CALL FOR QUESTIONS
  
 8) NOTE: PLEASE BE SURE THE ADDRESS FOR THE PROJECT IS
 LOCATED ON PLANS.
 THE ADDRESS WAS REDLINED ON PREVIOUS PLANS. 120
 CLEARWATER PK.
 FAC 61G15-23.002, FBC 106.5 FOR RECORD PLANS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  