Plan Review Notes
Plan Review Notes For Permit 09040659
Permit Number 09040659
Review Stop B
Sequence Number 1
Notes
Date Text
2009-05-19 09:58:23DENIED BY BUILDING
  
 1) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY CALCULATION FORM. FBC 13-103.1.2
  
 2) THE ENERGY CALCULATIONS DO NOT LIST THE INSULATION
 FOR THE SECOND FLOOR WOOD FRAME WALLS. PLEASE REVISE
 PLANS OR CALCULATIONS TO CORRESPOND. FBC 13-600
  
 3) SPECIFY THE MANUFACTURER AND TRUSS ANCHOR FOR THE
 ADDITIONAL STRAPPING ON THE PLANS. R802.1.6.5
  
 4) SHOW COMPLIANCE WITH R803.2.3.1 SHEATHING
 FASTENINGS. WOOD STRUCTURAL PANEL SHEATHING SHALL BE
 FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6
 INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER AT
 INTERMEDIATE FRAMING. WHERE ROOF FRAMING WITH A
 SPECIFIC GRAVITY, 0.42< G < 0.49 IS USED, SPACING OF
 RING-SHANK FASTENERS SHALL BE 4 INCHES ON CENTER IN
 NAILING ZONE 3 FOR 130 MPH OR GREATER DESIGN WIND
 SPEEDS IN ACCORDANCE WITH FIGURE R803.2.3.1.
  
 5) THE AGGREGATE AREA OF REPLACED GLAZING EXCEEDS 25
 PERCENT OF THE TOTAL AREA OF GLAZED OPENINGS IN THE
 DWELLING. SHOW COMPLIANCE WITH FBC EB 606.4 REPLACEMENT
 OF WINDOWS AND DOORS. THE REPLACEMENT OF GARAGE DOORS,
 EXTERIOR DOORS, SKYLIGHTS, OPERATIVE AND INOPERATIVE
 WINDOWS SHALL BE DESIGNED AND CONSTRUCTED TO COMPLY
 WITH CHAPTER 16 OF THE FLORIDA BUILDING CODE, BUILDING
 .
 EXCEPTIONS:
 1. OPENING PROTECTION EXCEPTION: FOR ONE- AND
 TWO-FAMILY DWELLINGS CONSTRUCTED UNDER CODES OTHER THAN
 THE FLORIDA BUILDING CODE AND LOCATED IN WIND-BORNE
 DEBRIS REGIONS, THE REPLACEMENT OF GARAGE DOORS AND
 EXTERIOR DOORS WITH GLAZING, SLIDING GLASS DOORS, GLASS
 PATIO DOORS, SKYLIGHTS AND OPERABLE AND INOPERABLE
 WINDOWS WITHIN ANY 12-MONTH PERIOD SHALL NOT BE
 REQUIRED TO HAVE OPENING PROTECTION BUT SHALL BE
 DESIGNED FOR WIND PRESSURES FOR ENCLOSED BUILDINGS,
 PROVIDED THE AGGREGATE AREA OF THE GLAZING IN THE
 REPLACED COMPONENTS DOES NOT EXCEED 25 PERCENT OF THE
 AGGREGATE AREA OF THE GLAZED OPENINGS IN THE DWELLING
 OR DWELLING UNIT. SUBMIT TWO COPIES OF PRODUCT
 APPROVALS AND INSTALLATION SCHEDULES FOR THE STORM
 PANELS. SEE SAMPLE SCHEDULE ATTACHED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]