Plan Review Notes
Plan Review Notes For Permit 09040613
Permit Number 09040613
Review Stop P
Sequence Number 1
Notes
Date Text
2009-05-06 19:08:241. FBC EXISTING BUIILDINGS VOLUME 2007 - 910.1 PLEASE
 PROVIDE A PLUMBING FIXTURE TABULATION FOR THE ENTIRE
 SPACE.
 2. FBC EXISTING BUILDINGS VOLUME 2007 - 906: PLEASE
 PROVIDE ENLARGED BATHROOM FLOOR PLANS WHICH REFLECT
 COMPLIANCE WITH CHAPTER 11 (ACCESSIBILITY) AS
 APPLICABLE, INCLUDE CLEAR FLOOR SPACE AND TURNING
 RADIUS OR "T" AREA.