2009-05-08 14:19:18 | *****DENIED***** |
| |
| |
| 1. THE PROJECT DATA STATES THAT SUITES #101 THRU #104 |
| WILL COMBINE TO CREATE ONE TENANT SPACE. WHAT WILL BE |
| THE SUITE DESIGNATION OF THIS TENANT SPACE? PLEASE BE |
| ADVISED THAT THE ACTUAL SITE LOCATION, INCLUDING THE |
| SUITE NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH |
| SUBMITTED PLAN SHEET. |
| |
| 2. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE |
| (BASED ON NFPA 101, LIFE SAFETY CODE, 2006 EDITION AND |
| NFPA 1, UNIFORM FIRE CODE, 2006 EDITION) SHALL BE |
| REFERENCED. PLEASE AMEND REFERENCE STANDARDS ON THE THE |
| TITLE SHEET. |
| |
| 3. PROVIDE A LIFE SAFETY PLAN SHOWING TRAVEL DISTANCE |
| TO THE EXIT(S) AND LOCATION OF THE 2A:10BC RATED FIRE |
| EXTINGUISHER(S). |
| |
| 4. PLEASE BE ADVISED THAT THE STAIRS SHALL HAVE |
| HANDRAILS ON BOTH SIDES. IF HANDRAILS/GUARDRAILS ARE TO |
| BE INSTALLED, PROVIDE PRESCRIPTIVE STRENGTH FOR THE NEW |
| GUARDRAILS AND HANDRAILS. |
| |
| 5. PROVIDE A FIRE SPRINKLER HEAD LAYOUT FOR THE |
| PROPOSED FLOOR LAYOUT. THESE HEADS MAY BE SHOWN ON THE |
| REFLECTED CEILING AND/OR THE LIFE SAFETY PLAN SHEET(S). |
| |
| 6. SPECIFY THE INTERIOR WALL AND CEILING FINISH |
| MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. |
| |
| 7. SPECIFY INTERIOR FLOOR FINISH IN TERMS OF CLASS I, |
| OR CLASS II. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER INDICATING WHERE/HOW THE COMMENTS WERE ADDRESSED |
| |
| |