Plan Review Notes
Plan Review Notes For Permit 09040613
Permit Number 09040613
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-05-08 14:19:18*****DENIED*****
  
  
 1. THE PROJECT DATA STATES THAT SUITES #101 THRU #104
 WILL COMBINE TO CREATE ONE TENANT SPACE. WHAT WILL BE
 THE SUITE DESIGNATION OF THIS TENANT SPACE? PLEASE BE
 ADVISED THAT THE ACTUAL SITE LOCATION, INCLUDING THE
 SUITE NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE
 (BASED ON NFPA 101, LIFE SAFETY CODE, 2006 EDITION AND
 NFPA 1, UNIFORM FIRE CODE, 2006 EDITION) SHALL BE
 REFERENCED. PLEASE AMEND REFERENCE STANDARDS ON THE THE
 TITLE SHEET.
  
 3. PROVIDE A LIFE SAFETY PLAN SHOWING TRAVEL DISTANCE
 TO THE EXIT(S) AND LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S).
  
 4. PLEASE BE ADVISED THAT THE STAIRS SHALL HAVE
 HANDRAILS ON BOTH SIDES. IF HANDRAILS/GUARDRAILS ARE TO
 BE INSTALLED, PROVIDE PRESCRIPTIVE STRENGTH FOR THE NEW
 GUARDRAILS AND HANDRAILS.
  
 5. PROVIDE A FIRE SPRINKLER HEAD LAYOUT FOR THE
 PROPOSED FLOOR LAYOUT. THESE HEADS MAY BE SHOWN ON THE
 REFLECTED CEILING AND/OR THE LIFE SAFETY PLAN SHEET(S).
  
 6. SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 7. SPECIFY INTERIOR FLOOR FINISH IN TERMS OF CLASS I,
 OR CLASS II.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE/HOW THE COMMENTS WERE ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722