Plan Review Notes
Plan Review Notes For Permit 09040613
Permit Number 09040613
Review Stop B
Sequence Number 1
Notes
Date Text
2009-05-06 18:51:121. FBC EXISTING BUILDINGS VOLUME 2007 - 912.8 :
 EXISTING BUILDINGS OR PORTIONS THEREOF UNDERGOING A
 CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE
 BUILDING.
 2. FBC 2007 11-4.1.6 ACCESIBILE BUILDINGS: ALTERATIONS:
 (1) (F) INSUFFICIENT INFORMATION HAS BEEN PROVIDED TO
 ESTABLISH THAT THE SECOND FLOOR AREAS IN THIS PROJECT
 ARE EXEMPT FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY PURSUANT TO EXCEPTION (3). PROVIDE SQUARE
 FOOTAGE TABULATIONS FOR THE GROUND FLOOR AND EACH OF
 THE THREE (3) SECOND FLOOR AREAS.
 3. FBC EXISTING BUILDINGS VOLUME 2007 - 912.4.2, 805, ,
 805.2, 805.3, 705.3, 705.3.2, DEMONSTRATE MEANS OF
 EGRESS IS COMPLIANT WITH APPLICABLE REQUIREMENT THROUGH
 A LIFE SAFETY PLAN, I.E., SINGLE EXIT. INCLUDE MEANS OF
 EGRESS LIGHTING, GUARDS AND RAILS ASSESSMENT.
 4. PROVIDE RECORDED UNITY OF TITLE FOR UNITS BEING
 CONNECTED.
 5. PROVIDE POA OR BUILDING OWNER'S CONSENT TO MODIFY
 SEPARATION WALLS WHICH DO NOT BELONG TO INDIVIDUAL
 PARCELS.
 PLEASE FEEL FREE TO CONTACT ME WITH QUESTIONS REGARDING
 THIS REVIEW.
 DOUG WISE - 561-805-6650
  