Plan Review Notes
Plan Review Notes For Permit 09040559
Permit Number 09040559
Review Stop B
Sequence Number 3
Notes
Date Text
2009-09-09 14:02:17****CORRECTIONS****
 ****REVISION, DESIGN PRESSURES PREPARED BY TARNOWSKI
 ENGINEERING***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 FROM PREVIOUS REVIEWS:
  
 1. FLOOR MOUNTS H AND I REQUIRE 3000PSI CONCRETE, SEE
 SHEETS 14, 15. INSTALLATION SCHEDULE NOTES THIS AS
 BLOCK.
  
 PLEASE FEEL FREE TO CONTACT ME TO DISCUSS.
  
 NEW:
  
 IT IS NOT CLEAR WHY NEW DESIGN PRESSURES WERE
 SUBMITTED; THIS DOES NOT ADDRESS THE COMMENT. FLOOR
 MOUNTS H AND I BOTH REQUIRE 3000 PSI CONCRETE. THE
 INSTALLATION SCHEDULE SUBMITTED BY THE CONTRACTOR
 STATES THAT THE SUBSTRATE IS BLOCK. EVEN IF THE
 SUBSTRATE IS CONCRETE, RESIDENTIAL PATIO SLABS ARE
 USUALLY 2500 PSI. PLEASE DEMONSTRATE HOW THE ANCHOR
 SPACING PROPOSED WILL COMPLY WITH DESIGN PRESSURE
 REQUIREMENTS.
  
  
  
  