Plan Review Notes For Permit 09040462 |
Permit Number |
09040462 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2009-09-02 16:56:08 | STRUCTURAL REVISION R-1 IS DENIED. | | | | 1) THE REVISED SHEETS ARE REQUIRED TO BE SIGNED AND | | SEALED BY THE ENGINEER OF RECORD. FS 471 | | | | 2) THE REVISED DRAWING DOES NOT CONTAIN ALL OF THE | | INFORMATION SPECIFIED IN THE SECTION OF THE ORIGINAL | | DRAWING THAT IT IS REPLACING. NOT ALL OF THE CONNECTORS | | SHOWN ARE SPECIFIED. | | | | 3) IF THE ENTIRE SHEET A-1.0 IS NOT REVISED, THE 8-1/2" | | X 11" REVISION SHOULD BE LABELED OR TITLED TO INDICATE | | THAT THE DRAWING IS REVISING PART OF A-1.O SHEET TO | | REFLECT FIELD CONDITIONS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|