2009-04-28 10:20:332007 FBC
 RE-ROOF
  
 DENIED BY BUILDING
  
 1) THE ENHANCED FASTENING SPECIFIED FOR THE CORNERS
 (ROOF ZONE 3) IS NOT ADEQUATE. THE ENGINEERING
 SPECIFIES 6"OC AT THE LAP AND TWO ROWS 6"OC IN THE
 FIELD, WHICH DOES NOT MEET THE -89 PSF UPLIFT THAT IS
 REQUIRED. CHECK RAS 117 CALCULATIONS.
  
 2) THE ENGINEERING REFERENCES THE 2004 FBC WITH 2007
 REVISIONS. THE 2007 FBC IS IN EFFECT AS OF MARCH 1,
 2009. ALSO THE 2007 FBC REFERENCES ASCE 7-05. PLEASE
 UPDATE SUBMITTALS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW