Notes |
Date |
Text |
2009-04-28 10:20:33 | 2007 FBC | | RE-ROOF | | | | DENIED BY BUILDING | | | | 1) THE ENHANCED FASTENING SPECIFIED FOR THE CORNERS | | (ROOF ZONE 3) IS NOT ADEQUATE. THE ENGINEERING | | SPECIFIES 6"OC AT THE LAP AND TWO ROWS 6"OC IN THE | | FIELD, WHICH DOES NOT MEET THE -89 PSF UPLIFT THAT IS | | REQUIRED. CHECK RAS 117 CALCULATIONS. | | | | 2) THE ENGINEERING REFERENCES THE 2004 FBC WITH 2007 | | REVISIONS. THE 2007 FBC IS IN EFFECT AS OF MARCH 1, | | 2009. ALSO THE 2007 FBC REFERENCES ASCE 7-05. PLEASE | | UPDATE SUBMITTALS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|