2009-05-11 16:57:20REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. SHEET 3: NO PROVISIONS ON PLAN FOR BALANCED RETURN
 AIR FROM BEDROOMS. PROVIDE BALANCED RETURN IN
 ACCORDANCE WITH FBC-M 601.4.
  
 2. SHEET 3: ONE OF TWO FLEX DUCTS FROM AHU CLOSET IS
 MISSING DUCT SIZE ON PLANS. PLEASE PROVIDE MISSING
 INFORMATION IN ACCORDANCE WITH FBC-M 603.1.
  
 3. SHEET 3: ELECTRICAL PLAN SHOWS NEW BATHROOM EXHAUST
 FAN. SHOW LOCATION OF BATH EXHAUST DISCHARGE TO
 DEMONSTRATE COMPLIANCE WITH FBC-M 401.4 AND FBC-M
 501.2.
  
 4. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL IN
 ACCORDANCE WITH FBC-M 307.2.1. ALSO, PROVIDE AUXILIARY
 DRAIN PROTECTION IN ACCORDANCE WITH FBC-M 307.2.3.
  