2009-05-11 16:57:20 | REVIEW #: 1ST | | ACTION: DENIED | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. SHEET 3: NO PROVISIONS ON PLAN FOR BALANCED RETURN | | AIR FROM BEDROOMS. PROVIDE BALANCED RETURN IN | | ACCORDANCE WITH FBC-M 601.4. | | | | 2. SHEET 3: ONE OF TWO FLEX DUCTS FROM AHU CLOSET IS | | MISSING DUCT SIZE ON PLANS. PLEASE PROVIDE MISSING | | INFORMATION IN ACCORDANCE WITH FBC-M 603.1. | | | | 3. SHEET 3: ELECTRICAL PLAN SHOWS NEW BATHROOM EXHAUST | | FAN. SHOW LOCATION OF BATH EXHAUST DISCHARGE TO | | DEMONSTRATE COMPLIANCE WITH FBC-M 401.4 AND FBC-M | | 501.2. | | | | 4. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL IN | | ACCORDANCE WITH FBC-M 307.2.1. ALSO, PROVIDE AUXILIARY | | DRAIN PROTECTION IN ACCORDANCE WITH FBC-M 307.2.3. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|