2009-05-04 15:22:20*****DENIED*****
  
 1. PROVIDE AN EXISTING FLOOR PLAN FOR THE PROJECT SITE.
 STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241, 2004
 EDITION.
  
 2. THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE
 (BASED ON NFPA 101, LIFE SAFETY CODE, 2006 EDITION AND
 NFPA 1, UNIFORM FIRE CODE, 2006 EDITION) SHALL BE
 REFERENCED.
  
 3. IF THE PROJECT SCOPE OF WORK IS TO BE DONE IN UNIT
 #1 ONLY OF THE ADDRESSED BUILDING, THE ADDRESS LISTED
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET SHALL
 INCLUDE THE UNIT NUMBER ALSO.
  
 4. PLEASE LIST THE EXISTING AS WELL AS THE NEW OCCUPANT
 LOAD BASED ON THE CHARACTERISTIC OF THE USE OF THE
 SPACE.
  
 5. SPECIFY THE INTERIOR FINISH MATERIAL FOR THE WALL
 AND CEILING (IN THE BEDROOMS) IN TERMS OF CLASS A,
 CLASS B, OR CLASS C.
  
 6. SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER.
  
 7. ON THE APPROPIATE EXTERIOR ELEVATION, DISPLAY/SHOW
 THE NUMERICAL ADDRESS FOR THIS BUILDING. AS PER WEST
 PALM BEACH CODE, THE NUMBERS SHALL BE NO LESS THAN 6"
 IN HEIGHT AND NO LESS THAN 1" IN WIDTH/STROKE. THE
 INDIVIDUAL DWELLING UNIT NUMBERS SHALL BE NO LESS THAN
 3" IN HEIGHT AND NO LESS THAN 1" IN WIDTH/STROKE.
  
 8. ON THE ELECTRICAL PLAN (SHEET 3), SMOKE DETECTORS
 ARE SHOWN AS BEING USED IN THE PROJECT SPACE. UNLESS
 THESE DEVICES ARE TIED INTO A FIRE ALARM SYSTEM FOR THE
 BUILDING, AMEND VERBAGE TO REFLECT THAT SMOKE ALARMS
 (SA), WHICH ALERT THE OCCUPANT OF THE SAID DWELLING
 UNIT ONLY, ARE TO BE USED.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE THE COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722