Date |
Text |
2009-05-01 09:58:16 | |
| |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 |
| REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED |
| PER 230.70, 225.32. INDICATE LOCATION ON PLAN PER |
| 230.72(A), 230.70 GENERAL. |
| MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN |
| A BUILDING OR OTHER STRUCTURE FROM THE SERVICE-ENTRANCE |
| CONDUCTORS. |
| THE AHJ HAS DETERMINED THAT "NEAREST POINT OF ENTRANCE" |
| SHALL BE NO FARTHER THAN 8' OF UNPROTECTED CONDUCTORS. |
| INDICATE COMPLIANCE WITH THIS ARTICLE ON THE PLAN. |
| 225.32 LOCATION. THE DISCONNECTING MEANS SHALL BE |
| INSTALLED EITHER INSIDE OR OUTSIDE OF THE BUILDING OR |
| STRUCTURE SERVED OR WHERE THE CONDUCTORS PASS THROUGH |
| THE BUILDING OR STRUCTURE. THE DISCONNECTING MEANS |
| SHALL BE AT A READILY ACCESSIBLE LOCATION NEAREST THE |
| POINT OF ENTRANCE OF THE CONDUCTOR |
| |
| 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. SUBMIT |
| THIS INFORMATION ON THE PLANS. |
| |
| 3} PER 230.2 ONE BUILDING SHALL BE SUPPLIED BY ONE |
| SERVICE. IT CAN HAVE UP TO SIX METERS, BUT ONLY ONE |
| SERVICE. REDRAW THE RISER DIAGRAM TO SHOW COMPLIANCE |
| WITH THESE ARTICLES. SHEET #4. |
| |
| 4} NOTES ON THE RISER DIAGRAM INDICATE THE GEC SYSTEM |
| ATTACHING TO "FOUNDATION REBAR", NOTE HOW THIS WILL BE |
| ACCOMPLISHED GIVEN THE BUILDING IS EXISTING. |
| |
| 5} IF THE LAUNDRY ROOM IS COMMON ELEMENT AREA THAT AREA |
| MUST CONTAIN ONLY WIRING FROM THE HOUSE PANEL PER |
| 210.25 COMMON AREA BRANCH CIRCUITS |
| BRANCH CIRCUITS IN DWELLING UNITS SHALL SUPPLY ONLY |
| LOADS WITHIN THAT DWELLING UNIT OR LOADS ASSOCIATED |
| ONLY WITH THAT DWELLING UNIT. BRANCH CIRCUITS REQUIRED |
| FOR THE PURPOSE OF LIGHTING, CENTRAL ALARM, SIGNAL, |
| COMMUNICATIONS, OR OTHER NEEDS FOR PUBLIC OR COMMON |
| AREAS OF A TWO-FAMILY OR MULTIFAMILY DWELLING SHALL NOT |
| BE SUPPLIED FROM EQUIPMENT THAT SUPPLIES AN INDIVIDUAL |
| DWELLING UNIT.*** NOTE ON PLANS WILL SUFFICE. |
| |
| 6} PER 210.8 (A) (6) THE ISLAND RECEPTACLES ARE |
| REQUIRED TO BE GFI PROTECTED- KITCHENS ??? WHERE THE |
| RECEPTACLES ARE INSTALLED TO SERVE THE COUNTERTOP |
| SURFACES |
| |
| 7} R313.1 SMOKE ALARMS. |
| SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING |
| LOCATIONS: |
| 1. IN EACH SLEEPING ROOM. |
| 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| VICINITY OF THE BEDROOMS. |
| A SMOKE ALARM IS REQUIRED IN THE HALL OUTSIDE OF |
| BEDROOMS #1 AND #2 TO MEET THE INTENT OF THIS |
| REQUIREMENT. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |
| |
| |