 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED
 PER 230.70, 225.32. INDICATE LOCATION ON PLAN PER
 230.72(A), 230.70 GENERAL.
 MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN
 A BUILDING OR OTHER STRUCTURE FROM THE SERVICE-ENTRANCE
 CONDUCTORS.
 THE AHJ HAS DETERMINED THAT "NEAREST POINT OF ENTRANCE"
 SHALL BE NO FARTHER THAN 8' OF UNPROTECTED CONDUCTORS.
 INDICATE COMPLIANCE WITH THIS ARTICLE ON THE PLAN.
 225.32 LOCATION. THE DISCONNECTING MEANS SHALL BE
 INSTALLED EITHER INSIDE OR OUTSIDE OF THE BUILDING OR
 STRUCTURE SERVED OR WHERE THE CONDUCTORS PASS THROUGH
 THE BUILDING OR STRUCTURE. THE DISCONNECTING MEANS
 SHALL BE AT A READILY ACCESSIBLE LOCATION NEAREST THE
 POINT OF ENTRANCE OF THE CONDUCTOR
  
 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. SUBMIT
 THIS INFORMATION ON THE PLANS.
  
 3} PER 230.2 ONE BUILDING SHALL BE SUPPLIED BY ONE
 SERVICE. IT CAN HAVE UP TO SIX METERS, BUT ONLY ONE
 SERVICE. REDRAW THE RISER DIAGRAM TO SHOW COMPLIANCE
 WITH THESE ARTICLES. SHEET #4.
  
 4} NOTES ON THE RISER DIAGRAM INDICATE THE GEC SYSTEM
 ATTACHING TO "FOUNDATION REBAR", NOTE HOW THIS WILL BE
 ACCOMPLISHED GIVEN THE BUILDING IS EXISTING.
  
 5} IF THE LAUNDRY ROOM IS COMMON ELEMENT AREA THAT AREA
 MUST CONTAIN ONLY WIRING FROM THE HOUSE PANEL PER
 210.25 COMMON AREA BRANCH CIRCUITS
 BRANCH CIRCUITS IN DWELLING UNITS SHALL SUPPLY ONLY
 LOADS WITHIN THAT DWELLING UNIT OR LOADS ASSOCIATED
 ONLY WITH THAT DWELLING UNIT. BRANCH CIRCUITS REQUIRED
 FOR THE PURPOSE OF LIGHTING, CENTRAL ALARM, SIGNAL,
 COMMUNICATIONS, OR OTHER NEEDS FOR PUBLIC OR COMMON
 AREAS OF A TWO-FAMILY OR MULTIFAMILY DWELLING SHALL NOT
 BE SUPPLIED FROM EQUIPMENT THAT SUPPLIES AN INDIVIDUAL
 DWELLING UNIT.*** NOTE ON PLANS WILL SUFFICE.
  
 6} PER 210.8 (A) (6) THE ISLAND RECEPTACLES ARE
 REQUIRED TO BE GFI PROTECTED- KITCHENS ??? WHERE THE
 RECEPTACLES ARE INSTALLED TO SERVE THE COUNTERTOP
 SURFACES
  
 7} R313.1 SMOKE ALARMS.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
 A SMOKE ALARM IS REQUIRED IN THE HALL OUTSIDE OF
 BEDROOMS #1 AND #2 TO MEET THE INTENT OF THIS
 REQUIREMENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  