2009-04-21 14:12:35****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PROVIDE ENGINEERING TO JUSTIFY PROPOSED DESIGN
 PRESSURES, FBC 1609. (+30S/-50S).
  
 2. PLEASE PROVIDE CERTIFICATION FOR THE BUILDING
 HEIGHT. YOU AHVE DECLARED A BUILDING HEIGHT OF 96 FEET;
 PAPA SHOWS THIS TO BE A 20+STORY BUILDING. OTHER
 CONTRACTORS STATE THAT THIS IS A 200' BUILDING.
  
 3. PLEASE COMPLETE THE INSTALLATION SCHEDULE. ANCHOR
 SPACING HAD "NOA" WRITTEN IN THAT COLUMN. THIS SHOULD
 BE THE ANCHOR SPACING IN INCHES PROPOSED. IT APPEARS
 THAT YOU PROPOSE 3.8".
  
 4. PLEASE COMPLETE THE COLUMN "SHUTTER MOUNTING
 CONNECTION TYPE." IT APPEARS THAT YOU PROPOSE TO USE
 AA.
  
 5. IF AA IS USED, TAPCON, MINIMUM EDGE DISTANCE
 IREQUIRED IS 3 1/8". PLEASE REVISE INSTALLATION
 SCHEDULE (2" PROPOSED; DOES NOT COMPLY WITH PRODUCT
 APPROVAL).
  
 6. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED,
 FAC9B72. THE PRODUCT APPROVAL FOR ROLLER STAR IS
 "VALIDATED," SHOULD SAY "APPROVED."