Plan Review Notes
Plan Review Notes For Permit 09040336
Permit Number 09040336
Review Stop E
Sequence Number 3
Notes
Date Text
2009-05-29 13:24:47** TEMP FAILED STATUS AS NEW SHEETS DO NOT CONTAIN ANY
 STAMPS FROM CITY PLACE MANAGMENT. THIS IS A CITY PLACE
 REQUIREMENT, NOT CITY OF WEST PALM BEACH. IF NO STAMP
 IS REQUIRED FROM CITY PLACE MANAGMENT OFFICE, PLEASE
 OBTAIN IN WRITING AND REVIEW WILL BE CHANGED TO A *P*
 STATUS. IF STAMP IS STILL REQUIRED THEN PLEASE HAVE
 PLANS STAMPED OR REPRESENTIVE FROM CITY PLACE OFFICE
 MAY COME IN AND STAMP AND SIGNS SHEETS.
 PLEASE CONTACT THIS OFFICE AS SOON AS POSSIBLE.
2009-05-29 13:21:42*** NOTES/ REDLINES/ PROVISO ****
  
 1) NOTE: THE CAROUSEL LIGHTING PANELS AS SHOWN ON PLANS
 SHALL BE FULLY LISTED AS A SIGN. 110.3, 13-415.AB.5,
 THE LISTING SHALL BE PER A NRTL/ SIGN LIGHTING
 MANUFACTURE IN ORDER TO MEET EXEMPTION FROM WATTAGE
 INPUT FOR FBC SECTION NOTED.
 EACH SIGN SHALL BE LISTED INDIVIDUALLY. MAY NOT BE A
 *TYPICAL* LISTING FOR ALL.
 ALL DOCUMENTS SHOWING LISTING ETC SHALL BE SUBMITTED TO
 THIS OFFICE FOR REVIEW PRIOR TO FINAL AND INSTALLATION.
 THIS WAS THE AGREEMENT WITH PLANS EXAMINER AND BUILDING
 OFFICIAL.
  
 2) NOTE: RISER SHOWS WHAT APPEARS TO BE A NEUTRAL FROM
 H PANEL TO TRANSFORMER. TRANSFORMER IS SEPARATELY
 DERIVED. ONLY PHASE CONDUCTORS AND EQUIPMENT GROUND IS
 INSTALLED. 250.6, 250.20,250.30
  
 3) NOTE: ALL FA DEVICES SHALL MEET FBC ADA,
 11-4.28.1-.4
  
 4) NOTE: ALL LOW VOLTAGE SYSTEMS SHALL BE UNDER
 SEPARATE PERMITS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  