2009-06-03 08:31:52BUILDING PLAN REVIEW
 PERMIT: 09040336
 ADD: 700 S ROSEMARY# 208
 CONT: SISCA
 TEL: (561)248-9041
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 JUNE 03/2009
 3RD REVIEW
 ACTION: REVIEWED
  
 1) THIS BUILDING IS A 5 STORY BUILDING (PARKING GARAGE
 PORTION) WHICH ENACTS THE FLORIDA STATE THRESHOLD LAWS:
 BUILDING CLASSIFICATION AS A BUILDING TYPE: I-B/ A2
 OCCUPANCY
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
  
 1B) THRESHOLD INSPECTOR:
 WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES
 DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL
 INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE.
 CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 1C) THRESHOLD BLDG, REQUIRED STATEMENT:
 W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE
 LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
  
 BUILDING PLAN REVIEW
 PERMIT: 09040336
 ADD: 700 S ROSEMARY# 208
 CONT: SISCA
 TEL: (561)248-9041
  
 BUILDING PROVISO:
 THESE FINISH MATERIAL REQUIREMENTS MUST BE MET BEFORE A
 CERTIFICATE OF COMPLETION CAN BE ISSUED.
  
 1) 803.6 TEXTILES. WHERE USED AS INTERIOR WALL OR
 CEILING FINISH MATERIALS, TEXTILES, INCLUDING MATERIALS
 HAVING WOVEN OR NONWOVEN, NAPPED, TUFTED, LOOPED OR
 SIMILAR SURFACE AND CARPET AND SIMILAR TEXTILE
 MATERIALS, SHALL COMPLY WITH THE REQUIREMENTS OF
 SECTION 803.6.1, 803.6.2 OR 803.6.3.
  
 803.6.1 SURFACE BURNING CHARACTERISTIC TEST. TEXTILE
 WALL AND CEILING COVERINGS SHALL HAVE A CLASS A FLAME
 SPREAD INDEX IN ACCORDANCE WITH ASTM E 84 AND BE
 PROTECTED BY AUTOMATIC SPRINKLERS INSTALLED IN
 ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2.
  
 803.6.2 ROOM CORNER TEST, TEXTILES. TEXTILE WALL
 COVERINGS SHALL MEET THE CRITERIA OF SECTION 803.6.2.1
 WHEN TESTED IN THE MANNER INTENDED FOR USE IN
 ACCORDANCE WITH THE METHOD B PROTOCOL OF NFPA 265 USING
 THE PRODUCT-MOUNTING SYSTEM, INCLUDING ADHESIVE.
  
 803.6.2.1 METHOD B TEST PROTOCOL. DURING THE 40 KW
 EXPOSURE, THE INTERIOR FINISH SHALL COMPLY WITH ITEM 1.
 DURING THE 150 KW EXPOSURE, THE INTERIOR FINISH SHALL
 COMPLY WITH ITEM 2. DURING THE ENTIRE TEST, THE
 INTERIOR FINISH SHALL COMPLY WITH ITEM 3.
  
 1. DURING THE 40 KW EXPOSURE, FLAMES SHALL NOT SPREAD
 TO THE CEILING.
  
 2. DURING THE 150 KW EXPOSURE, THE INTERIOR FINISH
 SHALL COMPLY WITH THE FOLLOWING:
  
 2.1. FLAME SHALL NOT SPREAD TO THE OUTER EXTREMITIES OF
 THE SAMPLES ON THE 8-FOOT BY 12-FOOT (203 MM BY 305 MM)
 WALLS.
  
 2.2. FLASHOVER, AS DESCRIBED IN NFPA 265, SHALL NOT
 OCCUR.
  
 3. THE TOTAL SMOKE RELEASED THROUGHOUT THE NFPA 265
 TEST SHALL NOT EXCEED 1000 M2.
  
 803.6.3 ROOM CORNER TEST, CEILING AND WALL FINISH.
 TEXTILE WALL AND CEILING COVERINGS SHALL MEET THE
 CRITERIA OF SECTION 803.2.1 WHEN TESTED IN THE MANNER
 INTENDED FOR USE IN ACCORDANCE WITH NFPA 286 USING THE
 PRODUCT-MOUNTING SYSTEM, INCLUDING ADHESIVE.
  
 2) FIBERGLASS LIGHT PANELS:
 2611.1 GENERAL. LIGHT-TRANSMITTING PLASTIC INTERIOR
 WALL SIGNS SHALL BE LIMITED AS SPECIFIED IN SECTIONS
 2611.2 THROUGH 2611.4. LIGHT-TRANSMITTING PLASTIC
 INTERIOR SIGNS SHALL ALSO COMPLY WITH SECTION 2606.
  
 2611.2 AGGREGATE AREA. THE SIGN SHALL NOT EXCEED 20
 PERCENT OF THE WALL AREA.
  
 2611.3 MAXIMUM AREA. THE SIGN SHALL NOT EXCEED 24
 SQUARE FEET (2.23 M2).
  
 2611.4 ENCASEMENT. EDGES AND BACKS OF THE SIGN SHALL BE
 FULLY ENCASED IN METAL.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.