Plan Review Notes
Plan Review Notes For Permit 09040336
Permit Number 09040336
Review Stop E
Sequence Number 2
Notes
Date Text
2009-05-08 15:29:07**DENIED PLANS**
  
  
  
 1) NOTE: COMPLIANCE WITH FBC 13-415.AB.5 CAN NOT BE
 DETERMINED.
 SOME LIGHTING ON PLANS IS STILL NOT COMPLETE.
 FOR EXAMPLE: PLEASE SEE ELEVATED DINING AREA WHICH
 LIGHTING PLANS SHOW SOME OF THE *D* FIXTURES TO LCP YET
 ON THE POWER PLANS THERE ARE *D* FIXTURES ARE NOT IN
 THE SAME LOCATION AND ARE NOT SHOWN CIRCUITED OR
 CONTROLLED BY LCP OR OTHER TYPE OF DEVICES.
 FOR EXAMPLE: PLEASE SEE G-1 FIXTURES WHICH BASED ON THE
 FIXTURE SYMBOLS AND NOTES ARE NOT DETERMINED AS ANY
 TYPE OF FIXTURE.
 FOR EXAMPLE: KITCHEN AREA LIGHTS CONTAIN NOTES ON PLANS
 WHICH MENTIONS TO CIRCUIT TO LCP HOWEVER THE PLANS DO
 NOT INDICATE ANY NEW OVER RIDES PER 13-415.AC.1.1,
 .1.2.
  
 2) NOTE: PLEASE SEE 700.12F FOR CIRCUITING IF EMERGENCY
 AND EXIT LIGHTS. THERE ARE NUMEROUS NEW FIXTURES WHICH
 DO NOT SHOW ANY TYPE OF CIRCUITING. THERE ARE SOME
 FIXTURES WHICH ARE NOT CIRCUITED TO THE LOCAL LIGHTING
 IN ANY ONE AREA. SEE SAME FOR EXIT SIGNS.
 SEE FIRE MARSHAL REVIEW COMMENTS FOR REQUIRED EXIT
 SIGNS. (UPPER BAR AREA) SEE NFPA-101 7.8, 7.9 SOME ARE
 MISSING.
  
 3) NOTE: PLEASE SEE ELECTRICAL RISER. THE RISER NEEDS
 TO BE COORDINATE WITH WHAT IS SHOWN ON RISER WITH
 PANELS. THERE ARE ALSO NEW CIRCUITS BEING ADDED TO
 PANELS SUCH AS PA WHICH THE PANEL SCHEDULE HAS NOT BEEN
 SUBMITTED. IN THE CONVERSATION WITH ELECTRICAL DESIGNER
 THE COMMENT WAS ONLY MADE TO THE EXISTING PANELS IN
 WHICH NO WORK WAS BEING DONE COULD BE DONE AS A
 PROVISO. HOWEVER THE PANELS IN WHICH THE PREDOMINANT
 AMOUNT OF WORK IS BEING DONE NEED TO COORDINATE WITH
 PLANS AND RISER.
 FOR EXAMPLE: PLEASE SEE RISER, ALL PANELS WITH THE
 EXCEPTION OF KA SECTION TWO ARE BEING FED FROM KA
 SECTION #1. HOWEVER BASED ON THE PANEL SCHEDULES FOR KA
 SECTION #1, THERE ARE NO PANELS LISTED.
 PLEASE COORDINATE.
  
 4) NOTE: PLEASE SEE MULTIPLE RECEPTACLES WITH NO
 CIRCUITING. SOME HAVE NOTES CLOSE TO THE DEVICE AND
 SOME ARE MISSING CIRCUITS.
 408.4, 240.4, 310.16, 220.14, 220.44
  
 5) NOTE: PANEL IN DEDICATE ELECTRICAL CLOSET STILL
 SHOWN ENCROACHING ON THE CLEAR SPACE REQUIRED PER
 110.26
  
 6) NOTE: PLEASE PROVIDE WHERE THE TRANSFORMER IS
 LOCATED IN THE ROOM SHOWN ON PLANS. IS THIS ON FLOOR?
 PLEASE SEE 450.13, 110.26, 450.9, 450.21B ETC.
  
  
 ** ANY AND ALL LOW VOLTAGE SHALL BE UNDER SEPARATE
 PERMITS, FEES AND PLANS.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH