2009-05-08 15:29:07 | **DENIED PLANS** |
| |
| |
| |
| 1) NOTE: COMPLIANCE WITH FBC 13-415.AB.5 CAN NOT BE |
| DETERMINED. |
| SOME LIGHTING ON PLANS IS STILL NOT COMPLETE. |
| FOR EXAMPLE: PLEASE SEE ELEVATED DINING AREA WHICH |
| LIGHTING PLANS SHOW SOME OF THE *D* FIXTURES TO LCP YET |
| ON THE POWER PLANS THERE ARE *D* FIXTURES ARE NOT IN |
| THE SAME LOCATION AND ARE NOT SHOWN CIRCUITED OR |
| CONTROLLED BY LCP OR OTHER TYPE OF DEVICES. |
| FOR EXAMPLE: PLEASE SEE G-1 FIXTURES WHICH BASED ON THE |
| FIXTURE SYMBOLS AND NOTES ARE NOT DETERMINED AS ANY |
| TYPE OF FIXTURE. |
| FOR EXAMPLE: KITCHEN AREA LIGHTS CONTAIN NOTES ON PLANS |
| WHICH MENTIONS TO CIRCUIT TO LCP HOWEVER THE PLANS DO |
| NOT INDICATE ANY NEW OVER RIDES PER 13-415.AC.1.1, |
| .1.2. |
| |
| 2) NOTE: PLEASE SEE 700.12F FOR CIRCUITING IF EMERGENCY |
| AND EXIT LIGHTS. THERE ARE NUMEROUS NEW FIXTURES WHICH |
| DO NOT SHOW ANY TYPE OF CIRCUITING. THERE ARE SOME |
| FIXTURES WHICH ARE NOT CIRCUITED TO THE LOCAL LIGHTING |
| IN ANY ONE AREA. SEE SAME FOR EXIT SIGNS. |
| SEE FIRE MARSHAL REVIEW COMMENTS FOR REQUIRED EXIT |
| SIGNS. (UPPER BAR AREA) SEE NFPA-101 7.8, 7.9 SOME ARE |
| MISSING. |
| |
| 3) NOTE: PLEASE SEE ELECTRICAL RISER. THE RISER NEEDS |
| TO BE COORDINATE WITH WHAT IS SHOWN ON RISER WITH |
| PANELS. THERE ARE ALSO NEW CIRCUITS BEING ADDED TO |
| PANELS SUCH AS PA WHICH THE PANEL SCHEDULE HAS NOT BEEN |
| SUBMITTED. IN THE CONVERSATION WITH ELECTRICAL DESIGNER |
| THE COMMENT WAS ONLY MADE TO THE EXISTING PANELS IN |
| WHICH NO WORK WAS BEING DONE COULD BE DONE AS A |
| PROVISO. HOWEVER THE PANELS IN WHICH THE PREDOMINANT |
| AMOUNT OF WORK IS BEING DONE NEED TO COORDINATE WITH |
| PLANS AND RISER. |
| FOR EXAMPLE: PLEASE SEE RISER, ALL PANELS WITH THE |
| EXCEPTION OF KA SECTION TWO ARE BEING FED FROM KA |
| SECTION #1. HOWEVER BASED ON THE PANEL SCHEDULES FOR KA |
| SECTION #1, THERE ARE NO PANELS LISTED. |
| PLEASE COORDINATE. |
| |
| 4) NOTE: PLEASE SEE MULTIPLE RECEPTACLES WITH NO |
| CIRCUITING. SOME HAVE NOTES CLOSE TO THE DEVICE AND |
| SOME ARE MISSING CIRCUITS. |
| 408.4, 240.4, 310.16, 220.14, 220.44 |
| |
| 5) NOTE: PANEL IN DEDICATE ELECTRICAL CLOSET STILL |
| SHOWN ENCROACHING ON THE CLEAR SPACE REQUIRED PER |
| 110.26 |
| |
| 6) NOTE: PLEASE PROVIDE WHERE THE TRANSFORMER IS |
| LOCATED IN THE ROOM SHOWN ON PLANS. IS THIS ON FLOOR? |
| PLEASE SEE 450.13, 110.26, 450.9, 450.21B ETC. |
| |
| |
| ** ANY AND ALL LOW VOLTAGE SHALL BE UNDER SEPARATE |
| PERMITS, FEES AND PLANS. |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |