Plan Review Notes
Plan Review Notes For Permit 09040336
Permit Number 09040336
Review Stop E
Sequence Number 1
Notes
Date Text
2009-04-17 18:42:41** DENIED **
  
  
  
 1) NOTE: PLANS NEED TO BE UNDER THE 2006 NFPA101. ALL
 PLANS SUBMITTED AFTER DECEMBER 31ST 2008
 FAC 69A-60.003, .004
 PLANS REVIEWED UNDER NFPA-101 2006, NFPA-70 2005 AND
 2007 FBC WITH 2009 REVISIONS.
  
 2) NOTE: PLEASE COMPLETE PLANS FOR ALL LIGHTING AND
 LIGHTING PERFORMANCE CALCULATIONS PER FBC 13-415.AB.5.
 PLANS MAKE REFERENCE TO 13-415.2.C.1, HOWEVER THAT CODE
 NO LONGER EXISTS IN THE CODE.
 PLEASE PROVIDE INFORMATION ON ALL LIGHTING FIXTURES
 SPECIFIC TO MANUFACTURE AND RATING OF FIXTURES.
 ALL FIXTURES SHALL BE INCLUDED IN THE CALCULATIONS
 UNLESS MEETING EXCEPTIONS. IF LIGHTING MEETS
 EXCEPTIONS, PLEASE IDENTIFY AND PROVIDE WHAT WILL MAKE
 THEM EXISTING.
 AS THERE IS MISSING INFORMATION A COMPLETE REVIEW CAN
 NOT BE DONE AT THIS TIME.
  
 ** PLEASE BE SURE ALL LIGHTING AS NOTED AND SHOWN
 CONTAINS A LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY. ( NRTL). 110.3
  
 3) NOTE: PLEASE SHOW COMPLIANCE WITH FBC 11-4.28.1,.2
 AND .3 FOR ADA COMPLIANCE.
  
 4) NOTE: PLEASE SUBMIT COMPLETE LOADS ON ALL PANELS.
 BELOW PANELS THERE ARE NOTES WHICH STATE ONLY NEW
 CIRCUITS ARE SHOWN. HOWEVER WITH THIS SAME STATEMENT
 THIS MEANS ONLY NEW LOADS ARE SHOWN AS NO OTHER LOADS
 ARE SHOWN.
 220.12,220.14,220.42, 220.43, 220.44 ETC
 PLEASE SEE 215.3, 230.42 FOR CONTINUOUS LOADS.
 ** PLEASE KEEP IN MIND THE SHOW WINDOW LOADS.
  
 5) NOTE: PLEASE COORDINATE ALL PANELS AND RISER
 DIAGRAM. PLEASE BE SURE TO COORDINATE WITH NOTES ABOVE
 FOR LOAD CALCULATIONS ALSO.
 THIS NOTE WILL BE BROKEN DOWN INTO MULTIPLE SECTIONS AS
 THERE ARE SEVERAL COORDINATION ITEMS WHICH NEED TO BE
 ADDRESSED.
  
 A) PLEASE SEE RISER AS PANEL *L* IS SHOW BEING FED FROM
 PANEL *KA SECTION 1* HOWEVER PER THE PANEL SCHEDULE
 SUBMITTED FOR THIS PANEL, NO PANEL *L* IS FED FROM THIS
 PANEL. PANEL *KA SECTION 2* ALSO DOES NOT LIST PANEL
 *L*.
  
 B) PLEASE SEE RISER AS PANEL *R* IS SHOWN BEING FED
 FROM *KA SECTION 1* HOWEVER BASED ON PANEL SCHEDULES OF
 BOTH SECTION ONE AND TWO, THE PANEL *R* IS ACTUALLY
 BEING FED FROM *KA SECTION 2*.
  
 C) PLEASE SEE RISER AS PANEL *KA SECTION * IS SHOWN
 BEING FED FROM *KA SECTION 2*. THIS SEEMS TO BE
 BACKWARDS AS THE SECTION 2 IS IN FRONT OF SECTION ONE.
 IN EITHER CASE NO MCB IS SHOWN IN SECTION ONE PANEL AND
 SECTION TWO PANEL WHICH IS SHOWN ON THE RISER AS ALL
 TAPPED CONDUCTORS SHALL TERMINATE IN OVER CURRENT
 PROTECTION. IN EITHER CASE A MAIN NEEDS TO BE
 INSTALLED. 240.21
 ALSO, WHICH PANEL IS ACTUALLY THE FIRST PANEL SECTION?
  
 D) PLEASE SEE RISER AS THERE ARE TWO LIGHTING CONTROL
 PANELS BEING SHOWN WHEN THERE IS ONLY ONE SCHEDULE
 SUBMITTED FOR ONE LIGHTING CONTROL PANEL.
  
 E) PLEASE COORDINATE ALL PANELS AND LOCATIONS OF ALL
 SERVICE EQUIPMENT. PLEASE SEE EQUIPMENT PLANS AS THE
 UNIVERSAL SYMBOL FOR AN ELECTRICAL PANEL INDICATES TWO
 PANELS WHICH ARE NOT ON ANY OTHER SHEETS. THESE ARE IN
 THE KITCHEN AREA NEAR EQUIPMENT NUMBERS 34,35.
 ARE THESE PANELS?
 WHERE IS PANEL PA?
 PLEASE SEE THE TWO LCP ON PLANS DO NOT MEET 110.26 AS
 BOTH ARE SHOWN WITH OVER LAP WHICH ONE WOULD AFFECT THE
 OTHER FOR CODE SECTION GIVEN. THESE MAY ALSO NOT BE
 LOCATED IN ANY TYPE OF STORAGE CLOSET.
 110.26, 240.24
  
  
 PLEASE GO OVER ALL PANELS, CIRCUITS, TAPPED CONDUCTORS,
 ETC. SOME ITEMS ARE NOTED FOR BENEFIT HOWEVER ARE NOT
 ALL ITEMS.
 240.21,215.5, 240.4, 310.16, 408.4, 408.36 ETC
  
 6) NOTE: ** NOTED FOR INFORMATIONAL PURPOSE. THE LOW
 VOLTAGE SYSTEMS AS SHOWN ON PLANS SUCH AS SPEAKERS,
 PHONE CATV SHALL BE REQUIRED TO BE UNDER SEPARATE
 PERMIT(S)
 THESE PLANS MAY BE REFERENCED FOR TURN AROUND PERMITS
 HOWEVER SEPARATE FEES AND PERMIT APPLICATION(S) ARE
 REQUIRED.
  
 7) NOTE: PLEASE BE SURE TO COMPLY WITH FBC
 13-415.1.AB.1.1, .1.2 AND .1.3 FOR LIGHTING CONTROLS.
 ** SEE SEPARATE CONTROLS**
 PLEASE ALSO SEE AREAS SUCH AS CORRIDOR WHICH DOES NOT
 INDICATE ANY OVER RIDE OR CONTROLS.
 ** IF USING ANY EXCEPTIONS FOR LIGHTS WHICH CAN NOT
 SEEN BY THE OCCUPANT, THEN PLEASE PROVIDE SPECIFIC
 DETAIL FOR ANY PROPOSED KEYPADS WHICH MUST
 CONTAIN*PILOT/INDICATOR LIGHTS*.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  