2009-06-01 17:05:52** DENIED 2ND REVIEW**
  
 1) NOTE: PLEASE SEE 13-415.AB.5 UNDER THE FBC 2007 WITH
 2009 REVISIONS.
 THE ADDITIONAL ALLOWANCE PREVIOUSLY PERMITTED FOR
 ACCENT, SCONCE LIGHTING ETC IS NO LONGER UNDER THE NEW
 CODE.
 THE AREAS ARE SPECIFIC TO SPACES. BASED ON THE
 ALLOWANCES UNDER THE NEW CODE, THE AMOUNT SHOWN EXCEEDS
 TABLES.
 THE FIXTURE SCHEDULE NEEDS TO COORDINATE. SEE WALL HUNG
 FIXTURE AS THIS STATES IT IS INCANDESCENT AND SHOWS A
 26W FLUORESCENT BULB. THIS IS NOT POSSIBLE.
 PLEASE BE SURE TO COME UP WITH SOME SORT OF FIXTURE
 MEETING MINIMUM CODE AT THIS TIME. FIXTURES MAY ALWAYS
 BE REVISED ALONG WITH THE TABLE CALCULATIONS AT A LATER
 DATE.
  
  
 ** AS GONE OVER WITH ENGINEER THE MOTION SENSORS WHICH
 ARE SPECIFICALLY STATED ON PLANS TO BE *MOTION ONLY*
 MAY ACTUALLY BE OCCUPANCY SENSORS WHICH ARE DUAL
 TECHNOLOGY.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  