2009-06-01 17:05:52 | ** DENIED 2ND REVIEW** |
| |
| 1) NOTE: PLEASE SEE 13-415.AB.5 UNDER THE FBC 2007 WITH |
| 2009 REVISIONS. |
| THE ADDITIONAL ALLOWANCE PREVIOUSLY PERMITTED FOR |
| ACCENT, SCONCE LIGHTING ETC IS NO LONGER UNDER THE NEW |
| CODE. |
| THE AREAS ARE SPECIFIC TO SPACES. BASED ON THE |
| ALLOWANCES UNDER THE NEW CODE, THE AMOUNT SHOWN EXCEEDS |
| TABLES. |
| THE FIXTURE SCHEDULE NEEDS TO COORDINATE. SEE WALL HUNG |
| FIXTURE AS THIS STATES IT IS INCANDESCENT AND SHOWS A |
| 26W FLUORESCENT BULB. THIS IS NOT POSSIBLE. |
| PLEASE BE SURE TO COME UP WITH SOME SORT OF FIXTURE |
| MEETING MINIMUM CODE AT THIS TIME. FIXTURES MAY ALWAYS |
| BE REVISED ALONG WITH THE TABLE CALCULATIONS AT A LATER |
| DATE. |
| |
| |
| ** AS GONE OVER WITH ENGINEER THE MOTION SENSORS WHICH |
| ARE SPECIFICALLY STATED ON PLANS TO BE *MOTION ONLY* |
| MAY ACTUALLY BE OCCUPANCY SENSORS WHICH ARE DUAL |
| TECHNOLOGY. |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |