Plan Review Notes
Plan Review Notes For Permit 09040291
Permit Number 09040291
Review Stop P
Sequence Number 1
Notes
Date Text
2009-04-30 14:40:53DENIED
 REFERENCE:
 FBC-2007 EXISTING BUILDING
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 11
  
 1. THE CODE CYCLE FOR ALL APPLICATIONS FOR PERMIT ON OR
 AFTER MARCH 1, 2009 IS FBC-2007 WITH 2009 SUPPLEMENTS.
 MANY SHEETS INCLUDING THE PLUMBING SHEET INDICATE THE
 DESIGN CRITERIA AS FBC-2004. PLEASE CORRECT ALL
 REFERENCES TO THE DESIGN CODE. SECTION 106.1.1.
  
 2. SHT A 120.1 THE DOOR TO THE ACCESSIBLE TOILET ROOM
 SHALL NOT SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR
 ANY FIXTURE. SECTION 11-4.22.2(1). IT APPEARS THAT THE
 DOOR SWINGS INTO THE CLEAR FLOOR SPACE FOR THE LAV AND
 THE W/C. PLEASE SHOW DOOR SWING FOR THIS TOILET ROOM.
  
 3. SHTS A 120.1 & A 210.1 (DETAILS 8 & 9. PLEASE SHOW
 THE 30" BY 48" CLEAR FLOOR SPACE REQUIRED FOR THE SINK
 ON THE FLOOR PLAN, AND THE KNEE CLEARANCE, (27"), AND
 THE SINK DEPTH, (6-1/2" MAX), AS REQUIRED IN SECTIONS
 11-4.24.3 & 11-4.24.4.
  
 4. SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING. SECTION 106.1.2 (MORE
 INFORMATION REQUIRED).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  