Plan Review Notes For Permit 09040291 |
Permit Number |
09040291 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-04-22 15:46:41 | *****DENIED***** | | | | | | 1. THE 2007 EDITION OF FLORIDA FIRE PREVENTION CODE | | (BASED ON NFPA 1 - UNIFORM FIRE CODE - 2006 EDITION AND | | NFPA 101 - LIFE SAFETY CODE - 2006 EDITION) SHALL BE | | REFERENCED. AMEND APPLICABLE CODES AND CODE ANALYSIS | | DATA ON THE APPROPIATE PLAN SHEETS AS NEEDED. | | | | 2. ON THE COVER SHEET UNDER APPLICABLE CODES, AMEND | | NFPA 13 TO REFLECT THE 2002 EDITION (CURRENTLY IN USE). | | | | 3. THE ACTUAL PROJECT SITE ADDRESS, INCLUDING THE SUITE | | NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED | | PLAN SHEET. | | | | 4. WILL THE SCOPE OF WORK HAVE CAUSE FOR THE FIRE | | SPRINKLER HEADS AND/OR FIRE ALARM DEVICES TO BE | | REMODELED? IF SO, SEPARATE PERMITS AND SHOP DRAWINGS | | WILL BE REQUIRED FOR THIS/THESE SYSTEM(S) AFTER THE | | MAIN PERMIT HAS BEEN ISSUED. | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE/HOW EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | | | |
|