Plan Review Notes
Plan Review Notes For Permit 09040291
Permit Number 09040291
Review Stop E
Sequence Number 1
Notes
Date Text
2009-04-27 13:56:17**DENIED PLANS**
  
  
 1) NOTE: PLANS SUBMITTED FOR PERMIT APPLICATION AFTER
 MARCH 1ST, 2009 SHALL BE UNDER THE DESIGN OF THE 2007
 FBC WITH 2009 AMENDMENTS. THIS INCLUDES ALL ADOPTED
 CODES AND REFERENCE STANDARDS IN FBC CHAPTER 35
  
 PLEASE SEE FAC 69A-60.003, AND .004 AS THE FOLLOWING
 NFPA REFERENCES WERE ACTUALLY ADOPTED ON DECEMBER 31ST,
 2008
 PLEASE ADJUST AS FOLLOWS.
  
 2007 FBC W/ 2009 REVISIONS.
 2006 NFPA-101
 2006 NFPA-1
 2005 NFPA-70
  
 THESE CODES NEED TO BE REFLECTED ON ELECTRICAL PLANS AS
 WELL AS THE A-SHEETS.
  
 ** PLEASE BE SURE ALL CODE REFERENCES ON PLANS REFLECT
 THE CURRENT ADOPTED CODES.
  
 2) NOTE: PLEASE COMPLETE FIXTURE LEGEND WITH FIXTURES
 SPECIFIC TO INSTALLATION. PLEASE EXPLAIN NOTE ON PLANS
 WHICH STATES * MAXIMUM LIGHTING WILL NOT APPLY IN THIS
 MODEL*.
 IT IS UNCLEAR HOW THE MINIMUM PRESCRIPTIVE FOR NEW
 BEING INSTALLED IS BEING NOTED AS NOT REQUIRED.
 13-415.2.AB.5
  
 3) NOTE: PLEASE EXPLAIN LIGHTING CONTROLS FOR NEW BEING
 INSTALLED. SOME LOCATION ALONG WITH NOTES MENTIONED THE
 USE OF *MOTION SENSORS*. THE MOTION SENSORS ARE NOT
 TYPICAL AND IN EITHER CASE MANY LOCATIONS INDICATE
 THESE DEVICES AND MANY ARE MISSING. AN EXAMPLE IS SOME
 OFFICE ROOMS.
 13-415.1.ABC.1.1, .1.2. (NEW ONLY)
  
 4) NOTE: PLEASE SEE FBC 1006.1.2, LS 101 7.8.1.2.2 AS
 OCCUPANCY SENSORS ARE REQUIRED TO BE FAIL-SAFE ON WHEN
 SELECTED TO CONTROL EGRESS LIGHTING IN EGRESS PATHS.
  
 5) NOTE: PLEASE BE SURE ALL CIRCUITING ON PLANS
 COORDINATE WITH THE SUBMITTED PANEL SCHEDULE AND PLEASE
 BE SURE THE PANEL SCHEDULE IS SPECIFIC TO ROOMS AND
 AREAS IN WHICH THEY FEED. STATING *LTS* OR RECEPTS* IS
 NOT PERMITTED.
 408.4
 AN EXAMPLE WOULD BE CIRCUITS 22 AND 24 HOWEVER THEY ARE
 NOT THE ONLY ONES.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  