Date |
Text |
2009-04-27 13:56:17 | **DENIED PLANS** |
| |
| |
| 1) NOTE: PLANS SUBMITTED FOR PERMIT APPLICATION AFTER |
| MARCH 1ST, 2009 SHALL BE UNDER THE DESIGN OF THE 2007 |
| FBC WITH 2009 AMENDMENTS. THIS INCLUDES ALL ADOPTED |
| CODES AND REFERENCE STANDARDS IN FBC CHAPTER 35 |
| |
| PLEASE SEE FAC 69A-60.003, AND .004 AS THE FOLLOWING |
| NFPA REFERENCES WERE ACTUALLY ADOPTED ON DECEMBER 31ST, |
| 2008 |
| PLEASE ADJUST AS FOLLOWS. |
| |
| 2007 FBC W/ 2009 REVISIONS. |
| 2006 NFPA-101 |
| 2006 NFPA-1 |
| 2005 NFPA-70 |
| |
| THESE CODES NEED TO BE REFLECTED ON ELECTRICAL PLANS AS |
| WELL AS THE A-SHEETS. |
| |
| ** PLEASE BE SURE ALL CODE REFERENCES ON PLANS REFLECT |
| THE CURRENT ADOPTED CODES. |
| |
| 2) NOTE: PLEASE COMPLETE FIXTURE LEGEND WITH FIXTURES |
| SPECIFIC TO INSTALLATION. PLEASE EXPLAIN NOTE ON PLANS |
| WHICH STATES * MAXIMUM LIGHTING WILL NOT APPLY IN THIS |
| MODEL*. |
| IT IS UNCLEAR HOW THE MINIMUM PRESCRIPTIVE FOR NEW |
| BEING INSTALLED IS BEING NOTED AS NOT REQUIRED. |
| 13-415.2.AB.5 |
| |
| 3) NOTE: PLEASE EXPLAIN LIGHTING CONTROLS FOR NEW BEING |
| INSTALLED. SOME LOCATION ALONG WITH NOTES MENTIONED THE |
| USE OF *MOTION SENSORS*. THE MOTION SENSORS ARE NOT |
| TYPICAL AND IN EITHER CASE MANY LOCATIONS INDICATE |
| THESE DEVICES AND MANY ARE MISSING. AN EXAMPLE IS SOME |
| OFFICE ROOMS. |
| 13-415.1.ABC.1.1, .1.2. (NEW ONLY) |
| |
| 4) NOTE: PLEASE SEE FBC 1006.1.2, LS 101 7.8.1.2.2 AS |
| OCCUPANCY SENSORS ARE REQUIRED TO BE FAIL-SAFE ON WHEN |
| SELECTED TO CONTROL EGRESS LIGHTING IN EGRESS PATHS. |
| |
| 5) NOTE: PLEASE BE SURE ALL CIRCUITING ON PLANS |
| COORDINATE WITH THE SUBMITTED PANEL SCHEDULE AND PLEASE |
| BE SURE THE PANEL SCHEDULE IS SPECIFIC TO ROOMS AND |
| AREAS IN WHICH THEY FEED. STATING *LTS* OR RECEPTS* IS |
| NOT PERMITTED. |
| 408.4 |
| AN EXAMPLE WOULD BE CIRCUITS 22 AND 24 HOWEVER THEY ARE |
| NOT THE ONLY ONES. |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |