2009-04-22 13:47:53 | BUILDING PLAN REVIEW |
| PERMIT: 09040291 |
| ADD: 4 HARVARD CIRCLE |
| CONT: FISHER CONTRACTING CORP |
| TEL: (561)691-4716 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| |
| * WEST PALM BEACH AMENDMENTS |
| |
| APRIL 22/2009 |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1A) : WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 1B) INFORMATIONAL FL S S 713.13 NOTICE OF COMMENCEMENT, |
| TO BE FILED WITH THE CLERK OF THE COURT. NOTE: |
| 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL & |
| VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. |
| |
| 1C) : PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| BUILDING WITH THE 20097 SUPPLEMENTS.PLEASE REVISE COVER |
| SHEET AND A120.1. |
| |
| 2) SHEET A120.1 INDICATES (3) NEW OFFICES, THE NEW |
| DOORS FAIL TO PROVIDE 18" ON THE PULL SIDE OF THE LATCH |
| PLEASE REVIEW 11-4. 13.6. |
| 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM |
| MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC |
| OR POWER-ASSISTED SHALL BE AS SHOWN IN |
| FIG. 25. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED |
| CLEARANCES SHALL BE CLEAR & LEVEL. |
| |
| 3) NEW HANDICAPPED RESTROOM SHOWN ON A120.1 DOES NOT |
| INDICATE ON SHEET A130.1 THAT THIS RESTROOM IS A |
| HANDICAPPED RESTROOM, PLEASE INDICATE AS SUCH. SHEET |
| A110.1 INDICATES THE REMOVAL OF SINK AND CABINET |
| INACTING DISPROPORTIONATE COST SECTION 11-4.1.6 (2)(A) |
| (III) AT LEAST ONE ACCESSIBLE RESTROOM FOR EACH SEX OR |
| A SINGLE UNISEX RESTROOM. |
| |
| 3A) SHEET A120.1 INDICATES THE REQUIRED FLOOR SPACE FOR |
| THE LAV AND WATER CLOSET. THE PLANS CLEARLY INDICATE |
| THE DOOR SWINGING INTO THE REQUIRED CLEAR FLOOR SPACE. |
| 1-4.22.2 DOORS.(1) ALL DOORS TO ACCESSIBLE TOILET ROOMS |
| SHALL COMPLY WITH SECTION 11-4.13. DOORS SHALL NOT |
| SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR ANY |
| FIXTURE. |
| |
| 3B) SHEET A500.1 INDICATES THE E3 DOOR THAT LEADS TO |
| THE NEW HANDICAPPED RESTROOM TO BE A 32 INCH DOOR |
| CREATING A 30 INCH OPENING. |
| 11-4.13.5 DOORWAY MIN CLEAR WIDTH . DOORWAYS SHALL HAVE |
| A MINIMUM CLEAR WIDTH OF 32" WITH THE DOOR OPEN |
| 90-DEGREES, MEASURED BETWEEN THE FACE OF THE DOOR AND |
| OPPOSITE STOP. |
| NOTE THIS IS WHERE THE DISPROPORTIONATE COST REQUIRING |
| A HANDICAPPED RESTROOM AND THE REMOVAL OF THE LAV AND |
| CABINET CREATE THE REQUIREMENT FOR THE WIDER DOOR. ALSO |
| NOTE THE LARGER DOOR WOULD ALSO SWING INTO THE CLEAR |
| FLOOR SPACE REQUIRED FOR THE LAV AND WATER CLOSET. |
| |
| 4) SHEET A130.1 DOOR# 2 TO THE RECEPTION AREA INDICATES |
| A NEW GLASS SIDE LIGHT, THE DOOR SCHEDULE NOR IS IT |
| PICKED UP WITH THE DETAIL 4/ A130.1 THIS REQUIRES |
| SAFETY GLAZING. 2406.3(6). |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)805-6731 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |