Plan Review Notes
Plan Review Notes For Permit 09040267
Permit Number 09040267
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-04-17 13:19:13***DENIED***
  
 1) THE FLOW TEST RESULTS ARE DATED 1/22/07. PLEASE
 PROVIDE RESULTS BASED ON INFORMATION TAKEN NOT GREATER
 THAN ONE YEAR FROM THE DATE OF PERMIT APPLICATION. IF
 NEW RESULTS ARE REQUIRED, CONTACT THE BUREAU OF FIRE
 PREVENTION AT (561) 804-4724.
  
 2) PLEASE VERIFY THAT THE SAFETY MARGIN OF THIS PROJECT
 IS NOT GREATER THAN 5.0 PSI.
  
 3) THE DOUBLE CHECK DETECTOR ASSEMBLY IS TO BE SECURED
 WITH A CHAIN AND LOCK IN ADDITION TO ELECTRONIC
 SUPERVISION.
  
 4) THE FIRE DEPARTMENT CONNECTION SHALL BE PROVIDED
 WITH KNOX LOCKING CAPS. AN APPLICATION IS AVAILABLE AT
 THE BUREAU OF FIRE PREVENTION. (561) 804-4724.
  
  
 MIKE WENNERGREN, ASST. FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756