Plan Review Notes For Permit 09040267 |
Permit Number |
09040267 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-04-17 13:19:13 | ***DENIED*** | | | | 1) THE FLOW TEST RESULTS ARE DATED 1/22/07. PLEASE | | PROVIDE RESULTS BASED ON INFORMATION TAKEN NOT GREATER | | THAN ONE YEAR FROM THE DATE OF PERMIT APPLICATION. IF | | NEW RESULTS ARE REQUIRED, CONTACT THE BUREAU OF FIRE | | PREVENTION AT (561) 804-4724. | | | | 2) PLEASE VERIFY THAT THE SAFETY MARGIN OF THIS PROJECT | | IS NOT GREATER THAN 5.0 PSI. | | | | 3) THE DOUBLE CHECK DETECTOR ASSEMBLY IS TO BE SECURED | | WITH A CHAIN AND LOCK IN ADDITION TO ELECTRONIC | | SUPERVISION. | | | | 4) THE FIRE DEPARTMENT CONNECTION SHALL BE PROVIDED | | WITH KNOX LOCKING CAPS. AN APPLICATION IS AVAILABLE AT | | THE BUREAU OF FIRE PREVENTION. (561) 804-4724. | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 804-4756 |
|