2009-04-14 14:24:44 | DENIED |
| REFERENCE: |
| FBC-2007 RESIDENTIAL |
| |
| A. THE FOLLOWING INFORMATION IS REQUIRED FOR GAS |
| PERMIT: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2007 |
| FUEL GAS CODE. THE PIPE SCHEMATIC SUBMITTED IN NOT IN |
| ISOMETRIC FORM. THE SCHEMATIC INDICATES THAT THE PE |
| POLY PIPE IS UNDERGROUND AND IF SO THE METER IS ALSO |
| SHOWN UNDERGROUND. THE RANGE COOKTOP PIPING IS NOT |
| CLEAR IN HOW IT WILL BE RUN. (SEE EXAMPLE OF ISOMETRIC |
| DRAWING). |
| |
| 2. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2007 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| |
| 3. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2007 FUEL GAS |
| CODE SECTION 304. |
| |
| 4. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2007 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - THE PLANS SHOW A |
| 2PSI METER, BUT INDICATES 12" WC AT THE APPLIANCES. IF |
| THE METER IS 2PSI THEN GAS REGULATORS WILL BE REQUIRED. |
| PLEASE CLAIFY. |
| |
| B. PLANS INDICATE THE WORK SHALL COMPLY WITH NFPA 54. |
| PLEASE BE ADVISED THAT NFPA 54 WAS NOT ADOPTED BY |
| FBC-2007 AND THAT THE DESIGN SHALL BE PER FBC-2007 |
| RESIDENTIAL/2007 FUEL GAS CODE. PLEASE CHANGE |
| REFERENCE. |
| |
| C. THE PERSON RESPONSIBLE FOR THE DRAWINGS SHALL PRINT |
| THEIR NAME AND PUT THEIR SIGNATURE ON THE PLANS. |
| SECTION 1-6.1.3. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |