Plan Review Notes For Permit 09040057 |
Permit Number |
09040057 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2009-04-20 10:44:26 | MONUMENTAL SIGN, BUILDING REVIEW CHECKLIST. | | REVIEW UNDER 2007 FBC. | | | | 1- DRAWINGS SUBMITTED DON'T PROVIDE ANY DESIGN CRITERIA | | AS REQUIRED BY SEC. 1604.2 FBC 2007. SPECIFY BUILDING | | CODE AND WIND LOADS USED FOR DESIGN (EG: FBC 2007 OR | | ASCE 7-05). SPECIFY VERTICAL REINFORCEMENT FOR MASONRY | | WALL. SPECIFY SIZE OF FOOTING AND REINFORCEMENT. | | SPECIFY CONSTRUCTION OF ARCHED OPENING. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|