2009-04-15 15:09:20 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2007 |
| FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| CODE |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FS FLORIDA STATUTE |
| |
| 1. INCORRECT ASCE-7 REFERENCE USED, FBC R43. |
| |
| 2. ENHANCED FASTENING CALCULATIONS SPECIFY INCORRECT |
| CODE VERSION (SHOULD BE FBC2007); PLEASE REVISE. |
| |
| 3. ENHANCED FASTENING, FRACTION OF INCH CANNOT BE USED |
| IN SPECIFICATION, RAS117 SECTION 9. |
| |
| 4. PROVIDE CALCULATIONS FOR ZONE 3 DESIGN PRESSURES. |
| SEE ASCE7-05 FIGURE 6-3 (ENCLOSED), ZONE 3, DESIGN |
| PRESSURE IS -89PSF FOR EXPOSURE B; YOU'VE DECLARED -72 |
| FOR ZONE 3, EXPOSURE C, SEE ALSO COMMENT #7. |
| |
| 5. SECTION 905.3 IS REFERENCED FOR SHINGLE |
| INSTALLATION; THIS IS FOR ROOF TILE INSTALLATION. |
| |
| 6. TWO DIFFERENT SHEATHING NAILING PATTERNS PROVIDED; |
| ONE DOES NOT COMPLY WITH FBC R803.2.3.1; SEE SHEET S3 |
| PLYWOOD NAILING DETAIL. |
| |
| 7. PLEASE SEE DEFINITION OF ENCLOSED BUILDING, |
| ASCE7-05. IT APPEARS THAT THIS PORTION OF THE BUILDING |
| WOULD BE DEFINED UNDER PARTIALLY ENCLOSED; PLEASE |
| EXPLAIN RATIONALE FOR ENCLOSED (AS EVIDENCED BY .18 |
| COEFFICIENT). |
| |