Plan Review Notes
Plan Review Notes For Permit 09040032
Permit Number 09040032
Review Stop B
Sequence Number 1
Notes
Date Text
2009-04-15 15:09:20****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. INCORRECT ASCE-7 REFERENCE USED, FBC R43.
  
 2. ENHANCED FASTENING CALCULATIONS SPECIFY INCORRECT
 CODE VERSION (SHOULD BE FBC2007); PLEASE REVISE.
  
 3. ENHANCED FASTENING, FRACTION OF INCH CANNOT BE USED
 IN SPECIFICATION, RAS117 SECTION 9.
  
 4. PROVIDE CALCULATIONS FOR ZONE 3 DESIGN PRESSURES.
 SEE ASCE7-05 FIGURE 6-3 (ENCLOSED), ZONE 3, DESIGN
 PRESSURE IS -89PSF FOR EXPOSURE B; YOU'VE DECLARED -72
 FOR ZONE 3, EXPOSURE C, SEE ALSO COMMENT #7.
  
 5. SECTION 905.3 IS REFERENCED FOR SHINGLE
 INSTALLATION; THIS IS FOR ROOF TILE INSTALLATION.
  
 6. TWO DIFFERENT SHEATHING NAILING PATTERNS PROVIDED;
 ONE DOES NOT COMPLY WITH FBC R803.2.3.1; SEE SHEET S3
 PLYWOOD NAILING DETAIL.
  
 7. PLEASE SEE DEFINITION OF ENCLOSED BUILDING,
 ASCE7-05. IT APPEARS THAT THIS PORTION OF THE BUILDING
 WOULD BE DEFINED UNDER PARTIALLY ENCLOSED; PLEASE
 EXPLAIN RATIONALE FOR ENCLOSED (AS EVIDENCED BY .18
 COEFFICIENT).
  